I/O connection, Digital input
a
Isolation to
All other ports
Connector
Detachable push-in terminal
Conductor cross section
0.2 -1.5 mm² (AWG 24 - 16)
Stripping length cable
10 mm
Circuit type
SELV
Maximum voltage/current
60 VDC, I
IN
≤
2.9 mA at 60 VDC
Voltage levels
Logic one: >8 VDC
Logic zero: <5 VDC
a
External circuits connected to I/O connectors shall be SELV-rated circuits, galvanic isolated from mains.
I/O connection, Relay output
a
Connect resistance
Maximum 30
Ω
Isolation to
All other ports
Connector
Detachable push-in terminal
Conductor cross section
0.2-1.5 mm² (AWG 24-16)
Stripping length cable
10 mm
Circuit type
SELV
Maximum voltage/current
60 VDC/80 mA
a
External circuits connected to I/O connectors shall be SELV-rated circuits, galvanic isolated from mains.
Ethernet TX
a
Electrical specification
IEEE std 802.3
Data rate
10 Mbit/s, 100 Mbit/s, 1000 Mbit/s, manual or auto
Duplex
Full or half, manual or auto
Circuit type
SELV
Transmission range
Up to 100 m with CAT5e cable or better
Isolation
All other ports
Cabling
Shielded cable CAT5e or better is recommended
Conductive chassis
Yes
a
10/100/1000 Mbit/s ports are no. 1 to 8
NOTE
The product is to be connected to internal Ethernet networks without
exiting a facility and being subjected to TNVs.
20
Lynx 5600 Series