![Westermo 3125-0150 Скачать руководство пользователя страница 7](http://html.mh-extra.com/html/westermo/3125-0150/3125-0150_user-manual_960495007.webp)
6
PS-60 User Guide 6125-2200
4. Technical Data
Input Data
Unless otherwise stated, all data applies for 25°C ambient temperature, 230 V AC input
voltage, and nominal output current (I
N
).
Input voltage range
100 V AC ... 240 V AC -15 % ... +10 %
110 V DC ... 250 V DC -20 % ... +40 %
Electric strength, max.
300 V AC 30 s
Frequency range (f
N
)
50 Hz ... 60 Hz -10 % ... +10 %
Current consumption (for nominal values)
typ.
0.85 A (100 V AC)
0.7 A (120 V AC)
0.39 A (230 V AC)
0.37 A (240 V AC)
0.75 A (110 V DC)
0.33 A (250 V DC)
The specified values for current consumption apply for operation in the static boost
(P
N
x 125%).
Discharge current to PE typical
< 0.25 mA (264 V AC, 60 Hz)
0.22 mA (264 V AC, 60 Hz)
Mains buffering
> 54 ms (120 V AC)
> 54 ms (230 V AC)
Typical response time
500 ms
Protective circuit
Transient surge protection Varistor
Switch-on current surge limitation typical
after 1 ms
4.3 A
Inrush surge current I
2
t
< 0.1 A
2
s
Input fuse slow-blow, internal
3.15 A
During the first few microseconds, the current flow into the filter capacitors is
excluded.
The SCCR value (short-circuit current rating) of the power supply unit corresponds
to the SCCR value of the backup fuse (see input protection table).