9
PS-60 User Guide 6125-2200
Output data
Nominal output voltage (U
N
)
24 V DC
Setting range of the output voltage (U
Set
)
(constant capacity)
24 V DC ... 28 V DC
Nominal output current (I
N
)
2.5 A
Static Boost (I
Stat.Boost
)
3.125 A (permanently up to 40°C)
Dynamic Boost (I
Dyn.Boost
)
5 A (available up to 60°C for 5 s)
Control deviation Static load change 10 %
... 90 %
< 0.5 %
Control deviation Dynamic load change 10
% ... 90 %, (10Hz)
< 2 %
Control deviation change in input voltage
±10 %
< 0.1 %
Short-circuit-proof
Yes
No-load proof
yes
Residual ripple (with nominal values)
< 40 mV
PP
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
Yes
Feedback resistance
≤ 35 V DC
Circuit breaker against surge voltage at
output by invasive foreign matter
≤ 32 V DC
Rise time typical
50 ms (U
Out
= 10 % ... 90 %)
Output connection data
Connection method
Screw connection
Conductor cross section, solid
0.14 mm² ... 2.5 mm²
Conductor cross section, flexible
0.14 mm² ... 2.5 mm²
Stranded conductor cross section with
ferrule
0.25 mm² ... 2.5 mm²
Conductor cross section AWG
26 ... 14
Stripping length
8 mm
Tightening torque
0.5 Nm ... 0.6 Nm
LED signalling
P
Out
> P
Thr
LED lights up yellow, output power > P
Thr
,
depending on the rotary selector switch
setting
U
Out
> 0.9 x U
Set
LED lights up green
U
Out
< 0.9 x U
Set
LED flashes green
Signal contact (adjustable)
Digital
0 / 24 V DC, 30 mA
Default
24 V DC, 30 mA (24 V DC for U
Out
> 0.9 x
U
Set
)
Signal connection data
Connection method
Screw connection
Conductor cross section, solid
0.14 mm² ... 2.5 mm²
Conductor cross section, flexible
0.14 mm² ... 2.5 mm²
Stranded conductor cross section with
ferrule
0.25 mm² ... 2.5 mm²
Conductor cross section
AWG 26 ... 14
Stripping length
8 mm
Tightening moment
0.5 Nm ... 0.6 Nm