030-101788 REV D 

1123-03D 

July 2, 2013 

Westell

 

 

Fuse Panel 

Technical Practice

 

 

NPTPA1123 

4/4 TPA + 5/5 GMT with Voltage/Current Readout 

 
 
 

 
 

FEATURES

 

  Compatible with +24V, +48V, -24V or -48V dc input voltages (battery voltages). 

  3-½ Digit LED display indicating Voltage/Current for either bus. 

  2 busses per panel (120 Amps/bus maximum). 

  5 GMT style fuses per bus (20 Amp GMT fuse max, 50 Amps per GMT bus max). 

  4 TPA style fuses per bus (50 Amp TPA fuse max, 120 Amps per TPA bus max). 

  Normal and Alarm LEDs for Bus A and Bus B indicate power or fuse failure. 

 

Two sets of “Form C” relay contacts extend alarm conditions for each bus.  

 

Brackets supplied are reversible for both 19” and 23” racks, with flush and offset mounting options. 

  H

igh current 1/4” stud inputs (1/4”studs on 5/8” centers) for up to 120 Amps/input. 

  Offset terminal blocks with rear shield provided (standard). 

  UL Listed 

Содержание NPTPA1123

Страница 1: ...ses per panel 120 Amps bus maximum 5 GMT style fuses per bus 20 Amp GMT fuse max 50 Amps per GMT bus max 4 TPA style fuses per bus 50 Amp TPA fuse max 120 Amps per TPA bus max Normal and Alarm LEDs fo...

Страница 2: ...if you do not wish to extend the alarms you don t have to do anything with the alarm pins The Normal condition of the relay exists when the panel is powered up without any blown fuses The local alarm...

Страница 3: ...nstalled for a flush mounting or 5 offset Adjust the position and orientation of the correct mounting brackets on the fuse panel such that it will fit the rack you wish to mount the panel in Please se...

Страница 4: ...ed to the rack ground From step 4 3 the panel should already be ground to the rack via the 12 24 thread forming rack screws and outside tooth lock washers In addition to grounding via the mounting bra...

Страница 5: ...12 A Yellow Green 15 A Red Blue 20 A Green White Table 4 12 1 Chassis Grounding Depending on the bus input current being supplied the chassis bonding conductor used should meet the minimum requirement...

Страница 6: ...Current Display 0 to 199 ADC 1 A resolution 3 We recommend that you size fuses such that they do not run at more than 70 of their rating Thus a 20A fuse should not be run at more than 14 A TPA fuses...

Страница 7: ...pment by anyone other than an authorized Westell representative will void the warranty 7 2 Westell will repair or replace any defective Westell equipment without cost during the warranty period if the...

Страница 8: ...__________________________________________________________________________________ 8 Noran Tel Mounting Options...

Страница 9: ...______________ 9 Noran Tel 1 2 3 4 C NC NO BUS A C NC NO BUS B ALARMS 9 8 7 6 5 9 8 7 6 5 1 2 3 4 A BAT RTN TPA TPA BAT A RTN GMT 9 8 7 6 5 GMT 9 8 7 6 5 BAT B RTN B BAT RTN TORQUE 1 4 STUDS TO 5 5 FT...

Страница 10: ...__________________________________________________________________________________ 10...

Отзывы: