5.  SPECIFICATIONS

 

5.1. Voltage 

 

-/+24 or -/+48 VDC Typical 

 

 

 

-/+22 to -/+58 VDC Max. 

5.2. Fuse Size   

60Vdc, 0.18 to 20 Amps Max* 
450A @60Vdc Interrupt rating 
(Littelfuse Type 481 Series) 

5.3. Current/Bus 

100 Amps Max.**  

5.4. Current/Panel 

200 Amps** 

5.5. Output Fuse 

GMT Style Fuse Holders 

5.6. Output/Bus  

10 Fuses (20 per panel) 

5.7. Output/Panel 

2 Busses per Panel 

5.8. Input Block  

Two ¼” Studs on 5/8 centers  
Max std lug is 1 AWG 
Max lug width = 0.710” 

5.9. Output Block 

#22 AWG to 12 AWG wire 
Or fork/ring for #6 screw, 
10AWG forks/rings will work 
Max lug width = 0.320” 

5.10. Alarm Block 

#6 screws at rear 

5.11. Relay Current 

1 Amps/58Vdc max 

5.12. Dimensions 

1¾ H, 17 W,2½ D 

5.13. Rack Mounting 

19” Racks for 1-1/4” 
Panel Spaces 

5.14. Weight 

 

 

Appx 4 Lbs 

5.15. Operating Temp.   

-40° to +65°C (Tma) 

    (-40°F 

to 

+149°F) 

5.16. Color 

 

 

Off White   

5.17 Interrupt Fuse Rating 

450A (max) 

 
*We recommend that you size fuses such that they do 
not run at more than 70% of their rating. Thus a 20A fuse 
should not be run at more than 14A. 
 
**The sum of the fuse ratings must not exceed the bus 
rating, or input fuse rating 
 
 

 
 
  

 
Compatible lugs for Input Block

 

2 hole compression lugs for 1/4” studs on 
5/8” centers (torque 5.5ft-lbs) example; 
Panduit® 

LCD1-14A  1awg wire 

       

LCD2-14A  2awg wire 

       

LCD4-14A  4awg wire 

       

LCD6-14A  6awg wire 

       

LCD8-14A  8awg wire 

 
The Panduit® CT-1700 crimping tool can be 
used for securing wire to any of these lugs. 
 
Input wiring should be rated 90°C or better 
and fused at 125% of total Bus current (ie: up 
to 125Amps MAX rated input fuse/breaker) 
 
 

Output lugs

 (locking fork recommended): 

Ring or fork for #6 screw (up to 10awg).  
(Torque to 9 in-lbs, use wire rated 90°C or 
better. 

  
NOTE:

 If fuse size is not specified in the 

equipment manual, fuses should be selected 
such that they do not run at more than 70% 
of their rating.  When installing fuses, the 
sum of the fuses installed in each bus should 
not exceed the bus rating (100 Amps) or 
input fuse rating.    

 
 
 
 

Chassis Grounding:  

 Depending on the bus input current being supplied, the chassis bonding 

conductor used should meet the minimum requirements.  Please note that 100 A is the maximum 
allowable bus current rating.   
 

Protective Current 

Rating 

Minimum AWG 

Recommended 

Compression Lug 

Minimum Wire 

Temperature rating 

0-40 Amps 

10 AWG 

Panduit, LCD10-14A 

90°C 

40-63 Amps 

8 AWG 

Panduit, LCD8-14A 

90°C 

63-80 Amps 

6 AWG 

Panduit, LCD6-14A 

90°C 

80-100 Amps 

4 AWG 

Panduit, LCD4-14A 

90°C 

 

 

Содержание NPGMT1125

Страница 1: ...es in each 20Amps GMT position max Polarity insensitive 24 or 48 Vdc battery voltage This panel can operate at 200 Amps of output current per panel 100 Amps per Bus Barrier terminal strips for fused o...

Страница 2: ...e alarm relay for that bus will change state These fuse panels have common C normally open NO and normally closed NC terminals for alarms for each bus Note the use of the alarm contacts is optional if...

Страница 3: ...ided WARNING For safety reasons all wiring should be done with the power source removed when possible Rack Mount Instructions Elevated Operating Ambient For closed or multi unit rack assemblies the op...

Страница 4: ...the panel should already be ground to the rack via the 12 24 thread forming rack screws and outside tooth lock washers In addition to grounding via the mounting brackets an appropriate cable size as...

Страница 5: ...ut fuse rating Compatible lugs for Input Block 2 hole compression lugs for 1 4 studs on 5 8 centers torque 5 5ft lbs example Panduit LCD1 14A 1awg wire LCD2 14A 2awg wire LCD4 14A 4awg wire LCD6 14A 6...

Страница 6: ...ipment by anyone other than an authorized Westell representative will void the warranty 7 2 Westell will repair or replace any defective Westell equipment without cost during the warranty period if th...

Страница 7: ...____________________________________________________________________________________ 7 Westell...

Страница 8: ...C NEG 24 VDC 9 9 Insert fuse flag down 20A MAX BUS B ACCEPTS C NC A A B B TRQ nuts to 5 5 ft lbs max TRQ nuts to 5 5 ft lbs max BAT RTN BUS B TRQ nuts to 3 ft lbs max BAT RTN BUS A NO is center alarm...

Страница 9: ...____________________________________________________________________________________ 9...

Отзывы: