background image

____________________________________________________________________________________

  

 

 

 

 

 

 

 

 

 

 

  

 

 

 

4

Note:

 The supply source must be limited to an 

instantaneous  short-circuit current not to exceed 
450 Amps. 
 

BAT

RTN

BUS B

9

10

BAT

RTN

 

Figure 4.4.1

 

 

4.4. The battery outputs (“BAT”) are available at 
the terminal blocks (#6 screw torque to 9 in-lbs, 
up to 10awg fork) at the rear of the panel.  Each 
fuse position is numbered and that circuit is 
available at the terminal block position with the 
same number. 
 
4.5. All battery return (“RTN”) connections are 
also terminated on barrier strips (#6 screw, up 
to 10awg fork).  Note that these returns are 
isolated from the chassis frame.   
 
4.6.  This panel has Bus A, and Bus B alarms.  
Each alarm has a common (C), normally open 
(NO) and normally closed (NC) alarm contact. 
In an alarm the “C” contact will short to the “NO” 
contact and the “NC” will open.  You can extend 
the alarm connections as per your alarm system 
requirements.  Westell recommends you fuse 
the alarm battery supply (ABS) to 1A or less to 
protect the alarm wiring and circuitry. 
 
4.7.  

CHASSIS GROUND;

  For safety reasons, 

and as recommended by NEBS, the chassis 
should be electrically connected to the rack 

ground.  From step 4.2. the panel should 
already be ground to the rack via the #12-24 
thread forming rack screws and outside tooth 
lock washers.  In addition to grounding via the 
mounting brackets, an appropriate cable size as 
outlined in section 5 (typically 10awg or larger) 
and the ¼” bolt and locks on rear of chassis 
(1/4” bolt torque;5.5ft-lbs or 7.5Nm) should also 
be used. Consult the National Electric Code, 
ANSI/NFPA, and Canadian Electrical code for 
AWG sizes.   
 
4.8.  Power up the panel by installing a Listed 
fuse/breaker rated for at least 60Vdc, with a trip 
rating of 125 Amps Max.

 

The panel should 

power up with the Normal Operation LED 

9

 

illuminated and without any red LEDs

!

 

illuminated, and the relays should be in the 
“Normal” state (“C” connected to “NC”).   
 
4.9.  If you wish to verify the fuse alarm circuit, 
you can insert a blown fuse into one of the 
empty fuse holders. The red Fuse Alarm 
LED

!

should light and the Normal 

Operation LED 

9

should extinguish and the 

appropriate alarm extension relay should 
change states to extend the alarm.   
 
4.10.  Install panel output distribution fuses as 
required. Be sure to size fuses to operate at no 
more than 70% of their rating (14A max for a 
20A fuse). Use the provided designation card to 
keep a record of which equipment is connected 
to which circuit and what the fuse rating is.  Be 
careful not to overload the panel bus or BDFB 
fuse position rating supplying the panel. 
 

 

 
 
 
 
 
 

Содержание NPGMT1125

Страница 1: ...es in each 20Amps GMT position max Polarity insensitive 24 or 48 Vdc battery voltage This panel can operate at 200 Amps of output current per panel 100 Amps per Bus Barrier terminal strips for fused o...

Страница 2: ...e alarm relay for that bus will change state These fuse panels have common C normally open NO and normally closed NC terminals for alarms for each bus Note the use of the alarm contacts is optional if...

Страница 3: ...ided WARNING For safety reasons all wiring should be done with the power source removed when possible Rack Mount Instructions Elevated Operating Ambient For closed or multi unit rack assemblies the op...

Страница 4: ...the panel should already be ground to the rack via the 12 24 thread forming rack screws and outside tooth lock washers In addition to grounding via the mounting brackets an appropriate cable size as...

Страница 5: ...ut fuse rating Compatible lugs for Input Block 2 hole compression lugs for 1 4 studs on 5 8 centers torque 5 5ft lbs example Panduit LCD1 14A 1awg wire LCD2 14A 2awg wire LCD4 14A 4awg wire LCD6 14A 6...

Страница 6: ...ipment by anyone other than an authorized Westell representative will void the warranty 7 2 Westell will repair or replace any defective Westell equipment without cost during the warranty period if th...

Страница 7: ...____________________________________________________________________________________ 7 Westell...

Страница 8: ...C NEG 24 VDC 9 9 Insert fuse flag down 20A MAX BUS B ACCEPTS C NC A A B B TRQ nuts to 5 5 ft lbs max TRQ nuts to 5 5 ft lbs max BAT RTN BUS B TRQ nuts to 3 ft lbs max BAT RTN BUS A NO is center alarm...

Страница 9: ...____________________________________________________________________________________ 9...

Отзывы: