background image

Section BXM‐161‐7HE‐20A

030‐101765 Rev. B

R

6

1311IARB

Figure 12.     Heat Exchanger Compartment Location

DO NOT remove the heat exchanger unless it is being replaced.
To replace/remove the heat exchanger, see Paragraph 5.2.

Heat

Exchanger

Unit

Air flow

cut‐out

holes

ry‐installed so approximately 5” of equipment space is available
from the inside of the closed front door to the channel (for up
to a 5” equipment projection), and approximately 12” of equip­
ment space is available behind the channel to the rear cabinet
wall. The channels can be moved forward 2” or backward 3”, if
a few additional inches of equipment depth is needed at either
the front or back of the channel. The slotted mounting brackets
for each channel contain seven holes which allow six channel
positions. Each rack channel also contains predrilled holes, with
standard hole spacings (either 1”, 1.75”, or 2” rack hole pat­
terns), to mount customer‐supplied equipment in the cabinet.
Network equipment up to 16 Rack Units (16 RUs = 28”) high
can be mounted on the internal rack inside the cabinet, either as
a single piece or multiple pieces of equipment.

‐ LEFT CHANNEL NOTE ‐

Access to the controller card may be limited if one of the front‐
most channel mounting positions is chosen for the left channel.

2.2.2

Door Sensor Switch

A door sensor switch is located at the bottom right corner of the
cabinet door opening (Figure 11). This switch is factory‐pre­
wired to the Controller Card for door alarm reporting purposes.
To temporarily disable the sensor, pull out the cylindrical door
switch actuator until it clicks. To re‐activate the sensor, either
gently push the actuator back in until a click is heard, or simply
close the cabinet door.

2.2.3

Cooling System / Heat Exchanger

The Boxer cabinet features an active heat‐exchange system that
compensates for the effects of internal equipment heat and ex­
ternal solar and temperature loading inside the cabinet. The two
heat exchanger fans (see location in Figure 12) are temperat­

Figure 11.     Door Sensor Switch Location

Door Switch
(prewired to

controller card)

 

ure activated. The fans turn on when the interior of the cabinet
reaches 35° C (95° F) and turn off when the internal cabinet
temperature cools to 25° C (77° F). At the core of the heat ex­
change system are numerous aluminum fins (visible through the
compartment's vent holes) on each “side” of a sealed divider
wall within the heat exchanger. The dual air‐path exchanger uses
the lower‐mounted fan to blow cool outside air past the “exterior
air side” fins of the heat exchanger and to direct the heated air
out the vent holes on the sides of the fan cover. Conversely, the
upper‐mounted fan circulates warm inside air down past the “in­
terior air side” fins of the heat exchanger and blows cooled air
into/through the main cabinet compartment. The heat ex­
changer unit is field‐replaceable (see Table 4 for part number).

2.2.4

Heat Exchanger Fans 

(“

FAN A” Connector)

Two, factory‐installed, temperature‐controlled fans (shown in
Figure 12) circulate air through the heat exchanger. One fan is
used for the external circuit, and one fan is used for the internal
circuit.

The internal fans perform as follows:

G

Off at ‐40°C  

G

50% on at 30°C 

G

100% on at 45°C

The external fans perform as follows:

G

Off at ‐30°C  

G

50% on at 40°C 

G

100% on at 55°C

Both of these fans are factory‐wired to the “FAN‐A” connector
on the controller card mounted on the left side wall of the cabi­
net, and are powered from either a field‐pr24VDC
power source or a ‐48VDC power source. The fans are not
field‐replaceable, and the heat exchanger housing the fans must
be replaced in the event of a unit failure (see Table 4).

2.2.5

Controller Card

Boxer‐16 includes a factory‐wired controller card located on the
inside left wall of the cabinet (Figure 13). The card includes con­
nections for the fans, temperature alarm, door alarm, and a 3A
fan fuse. Internal wiring has been factory‐wired. External wiring
to the power source and alarm monitoring equipment is done us­
ing “Euro‐connector” snap‐in terminal blocks which can be
disconnected from the controller card, and later re‐attached for
quick and easy connections. Table 2 lists all of the connectors
and positions on the controller card. The only installer connec­
tions are the TEMP ALARM, DOOR ALARM, and ‐48V and
GND for power connections. To make these connections to the

Figure 13.     Controller Card (Showing Euro‐connectors)

Isometric

View

Side View

Содержание Boxer BXM1619-7HE

Страница 1: ...ocu ment adds several G models to Table 4 adds the NESC OSHA note above adds the GR 487 Issue 4 compliant bullet list feature in Paragraph 1 5 for the 7HEG model and updates Figure 4 and Figure 6 to s...

Страница 2: ...Exchanger removable and replaceable 1 5 Product Features Each Boxer 16 cabinet comes fully assembled pre wired tested and ready for field provided customer equipment installation and includes the foll...

Страница 3: ...ns and vents Security is provided via a 2 point latch a tamper proof screw lock and a padlock hasp Side wall lift ears Paragraph 2 1 2 5 are provided for temporary installation lift assistance The bot...

Страница 4: ...ed for conve nient access to the rear of equipment mounted inside Boxer 16 The purpose of the access panel is to facilitate equipment ac cess cabling and servicing The panel is secured with six tamper...

Страница 5: ...ameter knock outs in the floor of the Boxer 16 cabinet where an option al battery box attaches to the cabinet hole patterns of both units match KNOCK OUT REMOVAL NOTE Always remove knock outs where ho...

Страница 6: ...nterior of the cabinet reaches 35 C 95 F and turn off when the internal cabinet temperature cools to 25 C 77 F At the core of the heat ex change system are numerous aluminum fins visible through the c...

Страница 7: ...card Two fans are wired to each set of terminals Shaded rows indicate installer connections TEMP ALARM DOOR ALARM and Power Table 2 Controller Card Connectors 2 2 6 AC Duplex GFI Outlets for Installe...

Страница 8: ...ectrostatic discharge procedures must be followed to maintain personal and equipment safety Do not store units near magnetic electromagnetic or electrostatic fields Always store or ship units in the o...

Страница 9: ...out from either direction per hole size WEIGHT NOTE The Boxer 16 cabinet weighs 80 pounds The weight of the inter nal equipment installed in the Boxer 16 should not exceed 90 pounds The mounting surf...

Страница 10: ...mbined weight of the cabinet and the equipment mounted inside the cabinet Westell recommends a minimum cabinet installation height of 30 from the ground 1 Find best wall position Locate the best mount...

Страница 11: ...ug 11 Determine next step or close up cabinet and clean the site Repeat Steps 6 8 of Paragraph 3 6 1 to determine the next step or finish the physical cabinet installation 3 6 3 Mounting on a Pole or...

Страница 12: ...it BXA PM02 Contents Threaded rod Bracket Washers and Nuts BXA PM03 kit also includes a shelf Figure 18 Boxer Mounted on Pole with Pole Mount Kit Pole Also see the instructions in the optional BXA PM0...

Страница 13: ...and gap less suppressors The pedestal shall be capable of accepting 120 240 volts single phase and provide hardware for mounting a power meter However Boxer 16 must only be supplied with 120 volts Fo...

Страница 14: ...hole pattern accommodates a wide variety of equipment and mounting bracket hole patterns Always follow company practices and the guidelines below when mounting equipment inside the cabinet 1 Verify th...

Страница 15: ...te and verify no equipment tie downs cables or wires will interfere with the closing of the door Clean up the installation site per company practice 3 18 Closing and Locking the Cabinet Upon completio...

Страница 16: ...mpartment from the door Make a written note of the length of the old power cord RETURN UNIT NOTE Return the old defective unit to Westell and receive a replace ment new unit see Paragraph 7 2 for deta...

Страница 17: ...ensor switch into its mount ing bracket from the rear side so the door sensor button protrudes through the hole for it at the front of the mount ing bracket press or snap it into place 6 Test Verify t...

Страница 18: ...optional battery box and pole mounted with the pole mount kit see Table 4 Table 3 Boxer 16 Cabinet Physical Specifications 8 SPECIFICATIONS 8 1 Electrical and Physical Specifications The Westellr Boxe...

Страница 19: ...on 48VDC A90 BXSC1619 4H Boxer 20 20 RU 19 wide rack Main Cabinet 400W heat exchanger always on 48VDC A90 BXM2019 4HE 400W heat exchanger temp controlled 24 or 48VDC A90 BXM2019 4HE3 Same as the 4HE...

Страница 20: ...0 101765 Rev B R 20 1311IARB Appendix A Product Views Figure 24 Bottom View of Boxer 16 Cabinet Showing Dimensions and Knock outs Mounting lift brackets door and heat exchanger not shown For mounting...

Страница 21: ...Section BXM 161 7HE 20A 030 101765 Rev B R 21 1311IARB Figure 25 Front Exterior View of Boxer 16 Cabinet 24 0 33 0 24 5 41 0 39 0 Rear View Panel On...

Страница 22: ...Section BXM 161 7HE 20A 030 101765 Rev B R 22 1311IARB Figure 26 Right Side Exterior View of Boxer 16 Cabinet 33 0 18 05 20 60 28 10 41 0...

Отзывы: