Fuse

The PWRguard PLUS fuse is used to protect the source and the load 

from excessive current.  The PWRguard PLUS includes a 40A fuse (the 

rating of the PWRguard PLUS.)  The fuse may be changed to a lower 

value if desired for protection of other system components downstream.

Operating In Automatic Reset Mode

The PWRguard PLUS unit is operational whenever it is connected to 

the 12V power source.  There is no ON/OFF switch needed. This is the 

Factory Default Mode Setting.

GREEN LED – 

Output ON

When the source voltage is between 11.0 and 

15.0V (nominally 13.8V), the large green LED will 

light showing that the output is ON. The small LED 

indicates the PWRguard PLUS is in Automatic Reset 

Mode.

RED LED – 

Hi-Fault

The RED LED (Hi-Fault) will light whenever the 

input voltage exceeds 15V.  The GREEN LED will 

go OFF and there will be NO output voltage.  In 

the automatic reset mode, the RED LED will turn 

off when the input voltage returns to less than 15V, 

and the output will turn ON, thereby relighting the 

GREEN LED and re-powering the load.

YELLOW LED– 

Low-Fault

The YELLOW LED (low-fault) will light whenever the 

input voltage drops below 11.0V.  This LED will also 

briefly light if there are momentary dips below 11.0V. 

This feature assures correct operation during turn-on 

surge currents and during SSB or CW transmission 

when powered from a battery supply. The voltage 

may drop each time the power requirement peaks. 

If the voltage continues to be below 11.0V for more 

than 5 seconds, the LED will light continuously. This 

state will continue until the voltage is continuously 

below 11.0V and indicates the battery is nearing its 

drained state. The GREEN LED will go OFF, thereby 

turning the output OFF.  The PWRguard PLUS will 

now remain OFF.  When the input voltage returns to 

13.0V, the PWRguard PLUS will automatically reset.

Operating In Manual Reset Mode

To configure this mode, hold the reset button down for 5 seconds and 

the small green “AUTO RESET” LED will go OFF.

Содержание PWRguard PLUS

Страница 1: ...tainradio com 1020 Spring City Drive Waukesha WI 53186 262 522 6503 sales westmountainradio com 2016 West Mountain Radio All rights reserved All trademarks are the property of their respective owners PWRguard PLUS ...

Страница 2: ...d if you do not need an audible alert Modes of Operation Automatic and Manual Automatic Mode Supply Voltage Not In Normal Range When the supply voltage is outside of the normal range the PWRguard PLUS will disconnect the load Upon restoration of normal supply voltage the load will be reconnected automatically Sense Input Triggered When the sense input is activated the PWRguard PLUS will disconnect...

Страница 3: ...inal post marked Buzzer 4 When the power supply is switched on the PWRguard Plus unit will become operational and the AUTO RESET and ON LEDs will both glow green If the AUTO RESET LED does not turn on hold the reset button down for 5 seconds until it does If the YELLOW LED Low fault comes on instead of the ON LED it means that your power supply or battery voltage is too low PWRguard Plus requires ...

Страница 4: ...0S output terminal and then plug the PWRguard PLUS output into the RIGrunner input terminal This will provide protection for the battery and all the devices that are plugged into the RIGrunner Additionally after loss of AC mains power the PWRguard PLUS will reset the system after the power is restored Integrated Set Up ...

Страница 5: ...reset mode the RED LED will turn off when the input voltage returns to less than 15V and the output will turn ON thereby relighting the GREEN LED and re powering the load YELLOW LED Low Fault The YELLOW LED low fault will light whenever the input voltage drops below 11 0V This LED will also briefly light if there are momentary dips below 11 0V This feature assures correct operation during turn on ...

Страница 6: ...low fault will light whenever the input voltage drops below 11 0V This LED will also light briefly if there are momentary dips below 11 0V This feature assures correct operation during turn on surge currents and during SSB or CW transmission when powered from a battery supply The voltage may drop each time the power requirement peaks If the voltage continues to be below 11 0V for more than 5 secon...

Страница 7: ...d off Red ON Voltage too high Blink Voltage good waiting for reset Yellow ON Voltage too low Blink Voltage good waiting for reset Short Interval Blink Battery Save Mode USB Programming Instructions Download and install the West Mountain Radio port diagnostics utility or use another terminal program such as Hyper Term During installation be sure to install the drivers on the PC The utility can be s...

Страница 8: ...st Mountain Radio diagnostics utility program Find the PWRguard Plus in the list of devices Right click on the PWRguard Plus and select TEST When the terminal window pops up press enter in the terminal area and the following menu will appear West Mountain Radio PWRguard 1 14 1 Reset to factory settings 2 View Change Settings 3 Monitor mode 4 Force output ON 5 Force output OFF Function 0 If enter 2...

Страница 9: ...to defects in workmanship or materials for one year after the date of purchase from West Mountain Radio Warranty does not cover damage caused by abuse accident misuse improper or abnormal usage failure to follow instructions improper installation alteration lightning or other incidence of excessive voltage or current If failure occurs within this period return the PWRguard Plus or accessory to Wes...

Страница 10: ......

Отзывы: