Section 2
Installation
Part Number: 9291463A 11/21
9
Installation Instructions
Installation Dimensions
Cabinet Interior Minimum Dimensions
Dimension
ASM-36P
ASM-48P
A
35.13” (89cm)
47.13” (120cm)
B
27.00” (69cm)
C
28.00” (71cm)
D
35.13” (89cm)
47.13” (120cm)
E
25.50” (65cm)
F
Min 0.75” (19cm)
17.00”
(42cm)
E
D
28.0”
(71cm)
10.0”
(25cm)
B
A
Air duct dimensions
to match condenser face
(Fig. 1)
4.37”
(11cm)
6.75”
(17cm)
3.5”(9cm) -
18”(46cm)
18.0”
(46cm)
Max
F
A
C
B
PREPARE THE CABINET
1. Install partitions between the Air Screen Merchandiser
and other electrical appliances if they are located in the
same cabinet. Partitions must fully extend front to back
and top to bottom.
2. Install a GFCI receptacle a minimum of 14” (36cm) up
from the cabinet bottom inside the partitions.
3. The unit requires airflow to the compressor. Two
louvers are provided with each unit.
NOTE: Any restriction to the proper air flow will void the
compressor warranty.
• Louver cut-outs are 28” x 17” (71cm x 42cm) cutouts.
• 143in2 (923cm2) is required at both the intake and
discharge.
• Louver cut-outs must extend to bottom of cabinet
and align with condenser face.
• Install the louvers on the front and back of the
cabinet.
Discharge Air
Fresh Air In On
Customer Side
Louver
Louver
Condenser
4. Cut a 6.75” x 4.37” (17cm x 11cm ) hole in the base on
the operator side for the control.
• The maximum distance between counter top and
the control cutout is 18” (46cm).
• The distance between the louver and the control
cutout must be between 3.50” (9cm) and 18” (46cm).
Operator Side
6.75” (17cm)
4.37” (11cm)
3.50" (9cm) Min
18" (46cm) Max
18" (46cm) Max