Installation and operating instruction
Oil condensing boiler WTC-OB 18-B
6 Operation
83311002 1/2018-03 La
45-132
6.4 Manual start up
Turn dial knob.
Tool bar appears.
Set the selection cursor below the chimney sweep symbol.
Press [ENTER].
The appliance starts according to the program sequence [ch. 3.3.5].
An
H
is sown in the display during oil preheating. Following the flame formation,
the display indicates the current flow temperature and the maximum capacity
(stage 2) will start.
1
1
1
2
1
Flow temperature
2
Capacity [kW]
Press [ENTER].
Set capacity required using dial knob.
The capacity started remains activated for 15 minutes.
Exit manual capacity setting
Press [ENTER].
You will exit manual capacity setting.
The last capacity set will remain activated for 2 minutes.
The time sequence of 2 minutes can be restarted by turning the dial knob in the
heating engineer level within this time. This provides the possibility of calling up
system values in the info level at the relevant capacity.
Display system values
Activate info level [ch. 6.3].
System values of the capacity most recently set can be displayed.