4 Control options
23-36
4.3 Room temperature dependent control
The flow temperature is controlled depending on the room temperat-
ure.
A room device or room sensor are required for room temperature de-
pendent control.
The current flow temperature setpoint is calculated from:
room setpoint temperature,
current room temperature,
room sensor influence.
The room setpoint temperature can be set in the user
.
The room sensor influence can be set in the Engineer level.
4.4 Weather compensated/Room control
The flow temperature of the heating circuit is controlled depending
on the external temperature and the room temperature.
An external sensor and room device or room sensor are required for
weather compensated control and room temperature dependent
control.
The current flow temperature setpoint is calculated from:
external temperature,
Heating curve:
Gradient
,
Parallel movement
,
room setpoint temperature,
current room temperature,
room sensor influence.
The heating curve and the room setpoint temperature can be set in
the user
The room sensor influence can be set in the Engineer level.