Installation and operating instruction
Oil burner WL40Z-A
4 Installation
83298002 3/2019-11 La
21-112
Nozzle selection table
Different load values are possible due to tolerances.
Burner capacity [kW] at pump pressure
Nozzle size [gph]
10 bar
11 bar
12 bar
13 bar
14 bar
1.35
60.7
64.3
66.6
69.0
72.6
1.50
67.8
71.4
73.8
77.4
79.7
1.65
75.0
78.5
82.1
85.7
88.1
1.75
78.5
83.3
86.9
90.4
94.0
2.00
90.4
95.2
98.8
102.3
107.1
2.25
101.2
107.1
111.9
116.6
120.2
2.50
113.1
119.0
123.8
128.5
133.3
2.75
123.8
130.9
135.7
141.6
146.4
3.00
135.7
142.8
148.8
154.7
159.5
3.50
158.3
165.4
173.7
180.9
186.8
4.00
180.9
189.2
198.7
205.9
213.0
4.50
203.5
213.0
222.5
232.1
240.4
5.00
226.1
236.8
247.5
257.0
266.6
5.50
248.7
260.6
272.5
282.0
292.7
6.00
271.3
284.4
297.5
309.4
320.1
Conversion of burner capacity to oil throughput see formula below.
Oil throughput in kg/h =
Burner capacity in kW
11.9 kWh/kg