8
Oil pump AT2 45C
•
Pump for distillate oil EL
•
Two ratings ranges
•
Two integral pressure regulating valves
•
One normally closed solenoid valve
➄
(stage 1); and
one normally open solenoid valve
➇
(stage 2)
•
Bypass plug for conversion from two pipe to single
pipe system
Technical data AT2 45C:
Pump pressure range _____________________8 to 25 bar
Supply rating ________________________________50 l/h
Factory setting ______1st stage 10 bar, 2nd stage 22 bar
Setting the atomising pressure
Pressure regulating screw
➅
for stage 1:
8 to 15 bar
Pressure regulating screw
➆
for stage 2:
12 to 25 bar
Clockwise rotation
= pressure increases
Anticlockwise rotation
= pressure decreases
Priming the pump
The pump primes itself automatically on two-pipe
installations. On one-pipe installations it is only possible to
prime the pump via the nozzle line or pressure test
connection
➄
, when the solenoid valve
➃
is open.
Oil hoses
Technical data:
Pressure class A, DIN 4798-1
DN ____________________________________________ 4
Length ______________________________________ 1200
Pump side connection* ______________________ G 1/8”
Installation side connection nipple ______________ G 3/8”
Nominal pressure____________________________ 10 bar
Test pressure ______________________________ 15 bar
Operating temperature ______________________ 70° C
* Fitting 6x1 with M10x1 union nut
➁
➀
➈
➆
➅
➇
➄
➃
➂
+
+
Oil Pump AT2 45C
➀
Return connection
➁
Suction connection
➂
Nozzle supply
➃
Pressure gauge con-
nection G 1/8”
➄
Solenoid valve stage 1
(normally closed)
➅
Pressure regulating
valve partial load
➆
Vacuum gauge con-
nection G 1/8”
➇
Solenoid valve stage 2
(normally open)
➈
Pressure regulating
screw full load
Converting pump (AT2 45C)
Two pipe system
One pipe system
(standard supply)
Bypass
plug
Closing plug