Installation and operating instruction
Dual fuel burner WGL40/1-A ZM
7 Commissioning
83273402 1/2019-02 La
71-148
2. Adjusting the operating points
Open oil shut off devices.
If a controlled shutdown or lockout occurs during setting:
Briefly press [G] and [L/A] keys simultaneously.
Press [+] key.
Combustion manager changes to setting level.
Plug in bridging plug No. 7 on combustion manager.
Burner starts in accordance with program sequence and stops in operating
point P
0
(ignition position).
Set pump pressure
The pump pressure must be set according to the nozzle selected [ch. 4.2].
Check pump pressure at pressure gauge.
Set pressure using pressure regulating screw
1
:
increase pressure: clockwise rotation,
decrease pressure: anticlockwise rotation.
1
Press [+] key.
Burner drives to operating point P
1
.
Press [+] key.
Burner drives to operating point P
9
.