Installation and operating instruction
Dual fuel burner WGL40/1-A ZM
7 Commissioning
83273402 1/2019-02 La
58-148
7.1.6 Preset pressure regulator
Determine setting pressure
Add the combustion chamber pressure in mbar to the setting pressure into the gas
butterfly valve.
Determine setting pressure from the table and note down.
The details given for calorific value H
i
relate to 0 °C and 1013 mbar.
The table values have been calculated under ideal conditions. The values are there-
fore guide values for basic settings.
Full load
[kW]
Setting pressure
into gas butterfly
valve
[mbar]
Min. connection pressure into isolating valve
[mbar]
(low pressure supply)
Nominal diameter valve train
¾"
1"
1½"
2"
DN 65 DN 80
W-MF
507
W-MF
512
W-MF
512
DMV
525
DMV
5065
DMV
5080
Natural Gas E: H
i
= 10.35 kWh/m
3
, d = 0.606
200
10.5
18
14
13
11
11
11
225
10.7
20
15
14
12
11
11
250
11.2
22
16
15
12
12
12
275
12.0
25
18
16
13
13
13
300
13.0
28
19
18
14
14
14
325
14.4
32
22
20
15
15
15
350
16.1
37
24
22
18
17
17
375
18.0
41
27
24
20
19
19
400
19.1
45
29
25
21
20
20
425
19.0
48
30
26
21
20
20
450
19.0
52
31
26
22
21
20
500
19.4
60
34
28
23
21
21
550
20.3
69
38
31
24
23
22
Natural Gas LL: H
i
= 8.83 kWh/m
3
, d = 0.641
200
12.3
23
17
16
14
14
14
225
12.7
26
18
17
15
15
14
250
13.3
29
20
18
16
15
15
275
14.1
33
22
19
17
16
16
300
15.3
37
24
21
18
17
17
325
16.7
42
26
23
20
19
19
350
18.3
47
29
26
22
21
20
375
20.3
53
33
29
24
23
22
400
21.0
58
35
30
25
24
23
425
21.3
63
37
32
26
24
23
450
21.7
69
39
33
26
25
24
500
23.0
81
44
37
28
26
25
550
24.8
94
50
41
31
29
27