10 Troubleshooting
83242002 1/2019-03 La
55-76
The following faults must only be rectified by qualified personnel:
Fault codes
Fault
Cause
Rectification
Flashing 4 times
Flame simulation/
extraneous light
Flame signal prior to or after
operation
Extraneous light source
present
Extraneous light detection
from 13 μA
Find and eliminate ex-
traneous light source
Flame sensor defective
Check flame sensor, if
necessary replace
Flame formation during pre-
purge
Solenoid valve leaking
Flashing 7 times
Flame failure during opera-
tion
Flame has failed
Oil supply leaking
Check oil supply
Suction resistance in front
of pump too high
Oil nozzle soiled
Replace oil nozzle
Flame signal insufficient
Burner setting incorrect
Check burner setting
Check flame signal
[ch. 7.1.1]
Flame sensor soiled
Clean flame sensor
Flame sensor defective
Check flame sensor, if
necessary replace
Flashing 8 times
Release contact fault
Temperature switch does
not close
Actuator defective
Check actuator, replace if
necessary
Temperature switch defect-
ive
Check temperature
switch and heat ex-
changer, if necessary
replace [ch. 9.9]
Flashing 10 times
Combustion manager fault
Burner does not start
Heat exchanger defective
Combustion manager de-
fective
Reset burner [ch. 10.1.2],
if fault reoccurs replace
combustion manager