The KNX IP Interface 731 supports up to 5 simultaneous con-
nections. For each connection a separate individual address is 
used. 

The first additional individual address is assigned by the ETS. By 
clicking on the 'Settings' at the selected connection "Local Set-
tings" this dialogue box with a corresponding input field appears: 

 

 

  
The further additional addresses can be assigned directly on the 

device. This is done by pressing the programming button 

❸ 

at 

least one second. Then, the programming LED flashes 

 and 

the addresses are assigned as follows: 

Connection 2 gets the next higher address than connection 1, 
connection 3 gets the next higher address than connection 2, 
etc.  

 

Example: 
 

Device address  

1.1.255  (address within ETS topology) 

Connection 1  

1.1.250  (address within local settings) 

Connection 2  

1.1.251  (assigned by programming button) 

Connection 3  

1.1.252  (assigned by programming button) 

Connection 4 

1.1.253  (assigned by programming button) 

Connection 5  

1.1.254  (assigned by programming button) 

 
The additional individual addresses have to be valid within the 
sub line of the KNX IP Interface and not be used by another 
device. By factory default only the additional individual address 
of the first connection is active (which is preassigned to 
15.15.250). To use more connections simultaneously, additional 
address assignment must be performed as described above. 

 

 

 

       WARNING 

 

 

The device may be built into distribution 
boards (230/400V). 

 

The device must be mounted and commis-
sioned by an authorized electrician. 

 

The prevailing safety rules must be heeded. 

 

The device must not be opened. 

 

For planning and construction of electric in-
stallations, the relevant guidelines, regulations 
and standards of the respective country are to 
be considered. 

 

 

Weinzierl Engineering GmbH

 

D-84508 Burgkirchen / Alz 

Germany 

http://www.weinzierl.de 

[email protected] 

2016/09/21

 

Содержание KNX IP Interface 731

Страница 1: ...lickering The Mode LED can visualize the status of each KNXnet IP tunneling connection With the buttons Conn Up Dn you can chose each single connection Conn Up counts the connection numbers up and Conn Dn down The actually selected connection number is indicated by flashing 1x 5x of the Mode LED An available KNXnet IP Tunneling connec tion is indicated by a green LED and a used tunneling connec ti...

Страница 2: ...50 1 additional address Connection 2 1 1 251 2 additional address Connection 3 1 1 252 3 additional address Connection 4 1 1 253 4 additional address Connection 5 1 1 254 5 additional address Section Individual Address enables you to change the individu al KNX address of the currently used KNXnet IP Tunneling connection To check if the address you want to assign is unique within your KNX installat...

Страница 3: ...programming mode on the device front can be activated by simultaneously pressing the buttons and The flushed programming button is always active and is not influenced by this parameter Manual operation on the device The manual operation of the KNX IP Interface 731 only contains the status display This parameter sets the duration of the manu al mode Upon completion the normal display mode is restor...

Страница 4: ...51 assigned by programming button Connection 3 1 1 252 assigned by programming button Connection 4 1 1 253 assigned by programming button Connection 5 1 1 254 assigned by programming button The additional individual addresses have to be valid within the sub line of the KNX IP Interface and not be used by another device By factory default only the additional individual address of the first connecti...

Отзывы: