background image

©

2016 WEINZIERL ENGINEERING GmbH 

Page 3/4

 

 

IP address 

Here the IP address of the KNX IP Interface 731 can be entered. 
This is used to address the device via the IP network (LAN). The 
IP addressing should be coordinated with the administrator of 
the network. 

Subnet mask 

Enter the subnet mask here. The device uses the values entered 
in this mask to determine whether there is a communication 
partner in the local network. If there is no partner in the local 
network, the device will not send the telegrams directly to the 
partner but to the gateway that routes the telegram. 

Default gateway 

Enter the IP address of the gateway here, e.g. the DSL router of 
the installation. 

Example of assigning IP addresses: 

A PC is used to access the KNX IP Interface 731: 

IP address of the PC: 

 

192.168.1.30 

Subnet of the PC:   

 

255.255.255.0 

The KNX IP Interface 731 is located in the same local LAN, i.e. it 
uses the same subnet. The subnet constrains the IP addresses 
that can be assigned. In this example, the IP address of the IP 
interface must be 192.168.1.xx, where xx can be a number from 
1 to 254 (with the exception of 30, which is already in use). It 
must be ensured that no numbers are assigned twice. 

IP address of the IP Interface:  

192.168.1.31 

Subnet of the IP Interface: 

 

255.255.255.0 

Remote access 

Remote access via the Internet is possible via the KNX IP Inter-
face 731. More details can be found in the document "Remote 
access with the ETS" at www.weinzierl.de

 

 

ETS parameter dialogue 

The following parameters can be set using the ETS.

 

General: 

 

Programming mode on device front  

The programming mode on the device front can be activated by 
simultaneously pressing the buttons 

❼ 

and

 ❽

. The flushed 

programming button 

❸ 

is always active and is not influenced by 

this parameter. 

Manual operation on the device 

The manual operation of the KNX IP Interface 731 only contains 
the status display. This parameter sets the duration of the manu-
al mode. Upon completion the normal display mode is restored. 

 

Programming 

The KNX IP Interface 731 can be programmed in different ways 
via the ETS:  

Via the KNX bus 

The device only needs to be connected to the KNX bus. The 
ETS requires an additional interface (for example, USB) to have 
access to the bus. Via this way both the individual address and 
the entire application including IP configuration can be pro-
grammed. Programming via the bus is recommended if no IP 
connection can be established. 

Via KNXnet/IP Tunneling 

No additional interface is required. Programming via KNXnet/IP 
Tunneling is possible if the device already has a valid IP configu-
ration (e.g. via DHCP). In this case the device is displayed in the 
interface configuration of the ETS and must be selected. The 
download is executed via the ETS project as with many other 
devices. 

 

Setting with ETS 3 

When using the ETS 3 (Version 3.0f) the 

setting of the device’s 

name and the setting of the IP configuration is done via the ETS 
parameter dialogue. 

The KNX IP Interface 731 can be selected in the Connection 
Manager as a programming interface. 

Select “Communication” 

within the menu item "Tools - Options": 

 

 

 
After clicking the 

button “Configure Interfaces” the ETS Connec-

tion Manager opens. You have to create a new connection type 
EIBnet/IP. The ETS begins with the automatic search of all 
KNXnet/IP devices. All found devices are displayed. Select the 
required device. 

 

Содержание KNX IP Interface 731

Страница 1: ...lickering The Mode LED can visualize the status of each KNXnet IP tunneling connection With the buttons Conn Up Dn you can chose each single connection Conn Up counts the connection numbers up and Conn Dn down The actually selected connection number is indicated by flashing 1x 5x of the Mode LED An available KNXnet IP Tunneling connec tion is indicated by a green LED and a used tunneling connec ti...

Страница 2: ...50 1 additional address Connection 2 1 1 251 2 additional address Connection 3 1 1 252 3 additional address Connection 4 1 1 253 4 additional address Connection 5 1 1 254 5 additional address Section Individual Address enables you to change the individu al KNX address of the currently used KNXnet IP Tunneling connection To check if the address you want to assign is unique within your KNX installat...

Страница 3: ...programming mode on the device front can be activated by simultaneously pressing the buttons and The flushed programming button is always active and is not influenced by this parameter Manual operation on the device The manual operation of the KNX IP Interface 731 only contains the status display This parameter sets the duration of the manu al mode Upon completion the normal display mode is restor...

Страница 4: ...51 assigned by programming button Connection 3 1 1 252 assigned by programming button Connection 4 1 1 253 assigned by programming button Connection 5 1 1 254 assigned by programming button The additional individual addresses have to be valid within the sub line of the KNX IP Interface and not be used by another device By factory default only the additional individual address of the first connecti...

Отзывы: