Caution 
Supply Voltage 
Condition 

Do not power the MT-600 and inductive DC loads, or input circuitry to the 
controller, with the same power supply. Note: The 24 VDC output from 
some controllers may not have enough current to power the MT-600. 

 

Caution  
Wire Routing 

Wire lengths should be minimized (Maximum 1600’ (500 m) shielded, 
1000’ (300 m) unshielded). 

Wires should be run in pairs with a neutral or common paired with a hot or 
signal line. 

If wiring is to be exposed to lightning or surges, use appropriate surge 
suppression devices. 

Keep AC, high energy, and rapidly switching DC wiring separate from 
signal wires. 

Equip ungrounded DC supplies with a resistor and capacitor in parallel to 
earth ground. This provides a path for static and high frequency dissipation. 
Typical values to use are 1MOhm and 4700pF. 

 

Connection 

To make a connection, strip about 3/8” of insulation off the end of the wire, 
turn the connector screw counterclockwise until the gap is wide open, insert 
the wire all the way in, and turn the screw clockwise until it’s tight. 

Connect positive DC line to the ‘+24V’ terminal and the DC ground to the 
‘0V‘ terminal. 

2.2.2 Grounding Requirements 

 

 

Chassis ground must be used.    DC ground is not directly coupled to Earth 
ground internally. It is preferable not to ground DC negative return to chassis 
ground as poor site earths can introduce noise into a system, but if necessary 
an earth connection should be made, from the power supply return point to 
the central star earth point. Ground conductors should be as short and as large 
in size as possible. The conductors must always be large enough to carry the 
maximum short circuit current of the path being considered. Ground 
conductors should be connected to a tree from a central star earth ground 
point. This ensures that no ground conductor carries current from any other 
branch. 

 

 

 

2.2.3 CE Requirements 

To make an MT-600 comply with EMC directives, and to reduce susceptibility to electrical 

interference, a separate #14 AWG ground wire should be taken to the chassis ground terminal of the 

power connector. This ground connection should be run directly to the central star earth connection 

point (as recommended in most Installation Instructions). 

2.2.4 Safety Guidelines 

This section presents recommended installation practices, and procedures. Since no two 

applications are identical, these recommendations should be considered as guidelines. 

 

Hardware 
Considerations 

WARNING! 

The system designer should be aware that devices in Controller systems could 
fail and thereby create an unsafe condition. Furthermore, electrical 
interference in an operator interface, such as an MT-600, can lead to 
equipment start-up, which could result in property damage and/or physical 
injury to the equipment operator. 

If you, or your company, use any programmable control systems that require 
an operator or attendant, you should be aware that this potential safety hazard 
exists and take appropriate precautions. Although the specific design steps 
depend on your particular application, the following precautions generally 

Содержание MT-615X

Страница 1: ...en tested to conform to European CE requirements This means that the circuitry is designed to resist the effects of electrical noise This does not guarantee noise immunity in severe cases Proper wire...

Страница 2: ...mmable gases vapors or dusts z The unit should not be installed where fast temperature variations and or high humidity are present This will cause condensation of water in the device z Do not install...

Страница 3: ...ower supply return point to the central star earth point Ground conductors should be as short and as large in size as possible The conductors must always be large enough to carry the maximum short cir...

Страница 4: ...intended as safeguards against the failure of critical components and the effects of such failures or the inadvertent errors that might be introduced if programs are changed while the equipment is in...

Страница 5: ...5 COM3 RS 485 COM3 RS 232 Pin assignment of the 9 Pin Female SUB D COM1 RS 485 COM3 RS 485 and COM3 RS 232 Port Pin Symbol Com1 RS485 2w Com1 RS485 4w Com3 RS485 Com3 RS232 1 Rx Data Rx 2 Rx Data Rx 3...

Страница 6: ...chinery Directive 89 392 EEC 91 368 EEC 93 44 EEC 93 68 EEC machine safety z MT600 products will be CE marked to indicate compliance with the EMC Directive The MT 600 Series has been designed to opera...

Страница 7: ...core processor Flash memory N A DRAM 256MB on board DDR 400MHz SDRAM CompactFlash card slot Type II x 1 RTC Built in General Specification Input Power 24 5 VDC Power Consumption 1A 24VDC CE Complies w...

Страница 8: ...5 2 4W COM3 RS232 USB HOST MINI USB PS 2 E G H I J K L M F Rear View Bottom View Side View Panel mounting clamp slots 10 places Cutout dimensions MT 615 352mm 13 86 W x 279mm 10 98 H D sub VGA out N A...

Отзывы: