2.1.2 Making a NEMA-4 Mounting 

Panel  
Details

 

The unit can be mounted into panels with a depth of 4”(105mm).    It is recommended that 
the unit be mounted on the front panel of a steel enclosure, through an appropriate opening. 
Allow a clearance of 1”(25mm) around the sides of the unit for mounting hardware. Allow 
clearance for cable connections to the back of the unit. Unit depth may vary according to 
cable type used. Typically, plan a depth to accommodate at least 4”(105mm) behind the 
panel. This device should be mounted in the vertical position and for use on the flat surface 
enclosure. 

NEMA-4 
Mounting

 

Put the unit through the panel cut out. Slide the clamps (packed with product) into every 
hole provided around the case. Tighten the clamping screws in an even pattern until the 
unit is secured in the panel. Screw Torque: 2.6~3.5 lbf.in. (For reaching waterproof effect 
and to prevent the panel from being deformed.) 

VESA 

Mounting 

There are 4 holes on back panel for locking VESA, The screw: M4 P0.7mm, length: 
shorter then 8.0mm, and screw torque: 2.6 lbf.in. 

Caution!

 

Do not over tighten mounting clamps! 

Note:

 

Specifications 

Note: To seal to NEMA-4 specifications, all supplied mounting clamps must be used and 
panel cannot flex more than 0.010”. 

2.1.3 Environmental Considerations 

 

z

 

The MT6070iH3 are to be used indoors as built in displays. Make sure that the displays 
are installed correctly and that the operating limits are followed (See Specifications). 

z

 

Do not operate the unit in areas subject to explosion hazards due to flammable gases, 
vapors or dusts. 

z

 

The unit should not be installed where fast temperature variations and/or high humidity 
are present. This will cause condensation of water in the device. 

z

 

Do not install these terminals in environments where have inflammable gases. 

2.2 Power Connections 

Make sure that all local and national electrical standards are met when installing the unit.   

Contact your local authorities to determine which codes apply. 

2.2.1 Power Requirements 

 

 

Power

 

The MT6070iH3 can be powered by DC power only. The specified 

voltage range is 

24±20%

 Volts DC. This insures compatibility with most 

controller DC systems.   
The power conditioning circuitry inside the unit is accomplished by a 

switching power supply. The peak starting current can be as high as 

700mA. 

 

Fusing 
Requirements

 

If the display does not come on within 5 seconds of power up, remove 

power. An internal fuse will prevent damage if the polarity of the DC 

power is incorrect. Check wiring to insure proper connections and try to 

power up again. 

 

Caution 
High Voltage

 

An Internal fuse will prevent damage for over voltage condition however 

it isn’t guaranteed. 
DC voltage sources should provide proper isolation from main AC power 

and similar hazards. 

 

Содержание MT-6070iH3 Series

Страница 1: ...es has been tested to conform to European CE requirements This means that the circuitry is designed to resist the effects of electrical noise This does not guarantee noise immunity in severe cases Proper wire routing and grounding will insure proper operation Mechanical Environment Avoid installing units in environments where severe mechanical vibration or shocks are present 2 0 Installation Instr...

Страница 2: ... z The MT6070iH3 are to be used indoors as built in displays Make sure that the displays are installed correctly and that the operating limits are followed See Specifications z Do not operate the unit in areas subject to explosion hazards due to flammable gases vapors or dusts z The unit should not be installed where fast temperature variations and or high humidity are present This will cause cond...

Страница 3: ...ot directly coupled to Earth ground internally It is preferable not to ground DC negative return to chassis ground as poor site earths can introduce noise into a system but if necessary an earth connection should be made from the power supply return point to the central star earth point Ground conductors should be as short and as large in size as possible The conductors must always be large enough...

Страница 4: ...only authorized personnel can make such changes These recommendations are intended as safeguards against the failure of critical components and the effects of such failures or the inadvertent errors that might be introduced if programs are changed while the equipment is in operation z The ICS 3 304 81 Safety Recommendations are reproduced by permission of the National Electrical Manufacturers Asso...

Страница 5: ...rnal device 2 3 4 USB Client port Mini USB cable RZCMT6100 is used to download projects from PC by the USB 2 0 client port Support USB 2 0 client interface The cable regulation must accord with HI SPEED USB Revision 2 0 SHIELDED Note Please do not connect HMI with PLC and PC simultaneously to prevent potential difference from destroying USB ports of HMI and PC How to install USB driver of HMI i se...

Страница 6: ...d 4 to ON position the rest of Dips remain on OFF position and then reboot MT6070iH3 Under this situation MT6070iH3 will jump to Touch Adjust Touch screen calibration mode After calibration the pop up window appears as the illustration below Users will be inquired if restoring the system password to the default value z When YES is chosen another pop up dialog appears as below Users will be confirm...

Страница 7: ... 2001 A2 2003 3 0 Specifications MT6070iH3 Hardware Specification Display 7 TFT LCD Brightness 350 cd m2 Color 65 536 colors Contrast Ratio 500 1 Resolution WxH dots 800 x 480 Back light LED Backlight life time avg 30 000 hr min Touch panel 4 wires resistive type Touch Accuracy Active Area Length X 2 Width Y 2 I O port COM1 RS 232 RS 485 2W 4W COM2 RS232 COM3 RS 232 RS 485 2W Ethernet port N A USB...

Страница 8: ... product has been maintained in a manner not conforming to product s instructions or has been modified in any way d If the serial number has been defaced or removed 4 0 Dimensions of MT 6070iH3 GME6070I1_MT6070iH3_Installation_120409 a DIP SW Reset button e Com1 RS485 Com3 RS485 Com3 RS232 b Fuse f Com1 RS232 Com2 RS232 c Power connector g USB Host port d VESA 75mm screw holes h USB Client port CO...

Отзывы: