Caution 

Supply Voltage 

Condition 

Do not power the MT-600 and inductive DC loads, or input circuitry to the 

controller, with the same power supply. Note: The 24 VDC output from 

some controllers may not have enough current to power the MT-600. 

 

Caution  

Wire Routing 

Wire lengths should be minimized (Maximum 1600’ (500 m) shielded, 

1000’ (300 m) unshielded). 
Wires should be run in pairs with a neutral or common paired with a hot or 

signal line. 
If wiring is to be exposed to lightning or surges, use appropriate surge 

suppression devices. 
Keep AC, high energy, and rapidly switching DC wiring separate from 

signal wires. 
Equip ungrounded DC supplies with a resistor and capacitor in parallel to 

earth ground. This provides a path for static and high frequency dissipation. 

Typical values to use are 1MOhm and 4700pF. 

 

Connection 

To make a connection, strip about 3/8” of insulation off the end of the wire, 

turn the connector screw counterclockwise until the gap is wide open, insert 

the wire all the way in, and turn the screw clockwise until it’s tight. 
Connect positive DC line to the ‘+24V’ terminal and the DC ground to the 

‘0V‘ terminal. 

2.2.2 Grounding Requirements 

 

 

Chassis ground must be used.    DC ground is not directly coupled to Earth 

ground internally. It is preferable not to ground DC negative return to chassis 

ground as poor site earths can introduce noise into a system, but if necessary 

an earth connection should be made, from the power supply return point to 

the central star earth point. Ground conductors should be as short and as large 

in size as possible. The conductors must always be large enough to carry the 

maximum short circuit current of the path being considered. Ground 

conductors should be connected to a tree from a central star earth ground 

point. This ensures that no ground conductor carries current from any other 

branch. 

 

 

 

2.2.3 CE Requirements 

To make an MT-600 comply with EMC directives, and to reduce susceptibility to electrical 

interference, a separate #14 AWG ground wire should be taken to the chassis ground terminal of the 
power connector. This ground connection should be run directly to the central star earth connection 
point (as recommended in most Installation Instructions). 

2.2.4 Safety Guidelines 

This section presents recommended installation practices, and procedures. Since no two 

applications are identical, these recommendations should be considered as guidelines. 

 

Hardware 
Considerations 

WARNING! 
The system designer should be aware that devices in Controller systems could 

fail and thereby create an unsafe condition. Furthermore, electrical 

interference in an operator interface, such as an MT-600, can lead to 

equipment start-up, which could result in property damage and/or physical 

injury to the equipment operator. 
If you, or your company, use any programmable control systems that require 

an operator or attendant, you should be aware that this potential safety hazard 

exists and take appropriate precautions. Although the specific design steps 

depend on your particular application, the following precautions generally 

Содержание MT-606SV1

Страница 1: ...has been tested to conform to European CE requirements This means that the circuitry is designed to resist the effects of electrical noise This does not guarantee noise immunity in severe cases Proper...

Страница 2: ...le gases vapors or dusts The unit should not be installed where fast temperature variations and or high humidity are present This will cause condensation of water in the device Do not install these te...

Страница 3: ...ower supply return point to the central star earth point Ground conductors should be as short and as large in size as possible The conductors must always be large enough to carry the maximum short cir...

Страница 4: ...l components and the effects of such failures or the inadvertent errors that might be introduced if programs are changed while the equipment is in operation The ICS 3 304 81 Safety Recommendations are...

Страница 5: ...3 RS485 2w 1 GND Signal Ground 2 Tx RS485 Transmit 3 Tx RS485 Transmit 4 Rx RS485 Receive Data 5 Rx RS485 Receive Data 6 GND Signal Ground 7 RxD Receive 8 TxD Transmit 9 Not used The Com3 RS485 2wire...

Страница 6: ...romagnetic emissions and immunity Machinery Directive 89 392 EEC 91 368 EEC 93 44 EEC 93 68 EEC machine safety MT500 products will be CE marked to indicate compliance with the EMC Directive The MT 600...

Страница 7: ...32bit RISC CPU 200MHz Flash memory 16MB 32MB DRAM 32MB 64MB CompactFlash card slot Type II x 1 RTC Built in General Specification Input Power 21 25 VDC Power Consumption 220 mA 24VDC CE Complies with...

Страница 8: ...anel Panel mounting clamp slots 4 places Cutout dimensions MT 606S CV1 192mm 7 56 W x 138mm 5 43 H Contrast Adjust VR DIP Switch Reset Button Ethernet SPK USB Client USB Host COM2 232 COM3 485 d a b c...

Отзывы: