Installation and Startup Guide

 

This document covers the installation of cMT2078X Series HMI, for the detailed specifications and 
operation, please refer to Datasheet, Brochure and EasyBuilder Pro User Manual. Please read all 
warnings, precautions, and instructions on the device carefully before use. 

Install Environment: 

NEMA Rating

 

The HMI product is UL Type 4X (NEMA 4) rated, indoor use only.

 

Electrical 
Environment

 

The 

HMI product has been tested to conform to European CE requirements. This 

means that the circuitry is designed to resist the effects of electrical noise. This 
does not guarantee noise immunity in severe cases. Proper wire routing and 
grounding will insure proper operation.

 

Environmental 
Considerations

 

(1)  Make sure that the displays are installed correctly and that the operating 

limits are followed. Avoid installing units in environments where severe 
mechanical vibration or shocks are present. 

(2)  Do not operate the unit in areas subject to explosion hazards due to 

flammable gases, vapors or dusts.

 

(3)  Do not install the unit where acid gas, such as SO2 exists. 
(4)  This device should be mounted in the vertical position and for use on the flat 

surface enclosure.

 

(5)  Conform to UL 61010-1 3rd ed. and UL 61010-2-201 2nd ed. safety 

requirement for use in Pollution Degree 2 Environment and dry location. 

(6)  Relative Humidity: 10% ~ 90% (non-condensing)

 

Cleaning 
Considerations 

Clean the device using dry cloths. Do not use liquid or spray detergents for 
cleaning. 

IP Rating 

IP 66 

 
Warning 

Protection impairment if used in a manner not specified by the manufacturer. 
Déficit de protection si utilisé d'une manière non spécifiée par le fabricant. 

Unpacking the Unit

 

Unpack and check the delivery. If damage is found, please contact the supplier.

 

 

NOTE: 

Place the operator panel on a stable surface during installation. Dropping it or letting it 

fall may cause damage. 

The package includes: 
(1) Installation Instruction, 2-sided A4 *1 (2) Human Machine Interface *1 (3) Power Connector *1 
(4) Brackets & Screws *1 pack (5) USB Stick Clamp & Tying Strap *1 

USB Stick Clamp Usage 

Combining the USB Stick with the clamp and the tying strap can prevent USB stick from disconnecting 
with HMI when strong vibration is present. 
1. Insert the USB connector to the clamp and tie them together with the tying strap. 
2. Press the spring and insert the USB stick into HMI. 

   

 

 

 

 

Installation Instructions 

Use a control box that provides enough stiffness. 
Cutout Dimension: 192 mm x 138 mm. Secure the 
operator panel in position, using all the fastening holes 
and the provided brackets and screws. Screw Torque: 
2.6 ~ 3.9 lbf.in. (For reaching waterproof effect and 
preventing the panel from being deformed.) 
Plan for adequate space around the unit and inside the 
enclosure, for ventilation and cables. Consider the 
heat from other devices inside the enclosure. The 
ambient temperature around the unit must be 0 ~ 55°C 
Minimum required clearances (along the overlay): Top 
/ Bottom / Sides 15 mm 
Maximum panel thickness: 4.5 mm 

Power Connections 

 

Power Connector Specifications:   
Wire AWG: 24~12 
Wiring Conductor Minimum Temperature: 75°C 
Screw Torque: 4.5 lbf-in (max.) 
Copper conduct only.

 

Spécifications du connecteur d'alimentation: 
AWG de fil: 24 ~ 12 
Température minimale du conducteur de câblage: 75°C 
Couple de vis: 4.5 lbf-in (max.) 
Conducteur en cuivre seulement

 

NOTE:   

1. Connect positive DC line to the ‘+’ terminal and the DC ground to the 
‘-’ terminal. 
2. When downloading project using a USB cable, do not connect HMI 
with PLC and PC simultaneously, for electric potential difference may 
result in damage to HMI or PC.

 

 

System Settings 

When HMI is powered up and displays image, press the 
round Start Button in the upper-left corner of the screen to 
open the Setting dialog box. Tap the lock icon 

  and log 

in. (Default System Password: 111111) 
Go to the Network tab, and setup your network. 
In Setting dialog box you can see device information, 
configure general settings, set HMI Time/Date/Name, and 
more. 
 

EasyBuilder Pro Software Settings 

 

Launch EasyBuilder Pro software, select your project file, 
press F7 shortcut key to open the download dialog box: Select Ethernet > IP tab > Enter your HMI IP > 
Click Download to download this project file to HMI.   
Using screensaver and backlight saver is recommended in order to avoid image persistence caused 
by displaying the same image on HMI for a long time. 
(Please refer to EasyBuilder Pro User Manual for software operation details.) 
 