cMT-CTRL01 User Manual 

 

V1.0.1

 

 

CPU LED 

RUN   

ERR   

Description 

OFF 

OFF 

CODESYS STOP 

ON 

OFF 

CODESYS RUN 

Blinking 

OFF 

EBPro or CODESYS scans and the LED of the found unit 
winks. 

OFF 

ON 

CODESYS ERROR 

Blinking 

Blinking 

BOOT 

 

IO LED 

RUN   

ERR   

Description 

OFF 

OFF 

Power off or no power 

Blinking 

OFF 

IO initiating 

Blinking 

ON 

IO initiation error 

ON 

OFF 

IO working 

ON 

Blinking 

IO module alarm 

ON 

ON 

IO communication fault 

Blinking 

Blinking 

Exceeds power limitation or too many modules 
connected. 

 

Ethernet 

 

 

Color   

Status 

Orange 

LAN connection status 

Green 

LAN communication status 

 

1.6.

 

Battery 

cMT-CTRL01 requires a CR1220 3V lithium battery to keep the RTC running. 

Battery Specification: UL Certification Battery, Type CR1220, Rated 3V, Max. Abnormal Charging 
Current 10mA, Working Temperature: max. 70

°

Battery replacement shall be performed by qualified personnel (Engineer) only and care must be 

taken when handling lithium batteries. For more information on battery replacement and disposal 

considerations, please refer to the following link:   

http://www.weintek.com/download/MT8000/eng/FAQ/FAQ_103_Replace_Battery_en.pdf

 

 

1.7.

 

Power connection 

Power:

 The unit can be powered by DC power only, the voltage range is compatible with most 

controller DC systems. The power conditioning circuitry inside the unit is accomplished by a 
switching power supply. The peak starting current can be as high as 500mA. 

cMT-CTRL01 voltage range: 24±20% VDC 

Содержание cMT CTRL01

Страница 1: ...User Manual V1 0 1...

Страница 2: ...ory 9 2 3 5 Email 10 2 3 6 Project Management 10 2 3 7 System Password 11 2 3 8 Enhanced Security 11 2 3 9 EasyAccess 2 0 Optional 12 2 3 10 OPA UA 12 2 3 11 Communication 12 Updating Web Package and...

Страница 3: ...Project 36 Chapter9 9 1 Creating Tags 36 9 2 Exporting Tags 36 9 3 Configuring EasyBuilder 37 Connecting cMT CTRL01 CODESYS to iR Series Modules 38 Chapter10 Connecting cMT CTRL01 to iR ETN 41 Chapte...

Страница 4: ...AN 1 10 100 1000 Base T x 1 LAN 2 10 100 Base T x 1 COM Port COM1 RS 232 2W COM2 RS 485 2W 4W COM3 RS 485 2W Local bus iBus CAN Bus N A RTC Built in Power Input Power 24 20 VDC Power Isolation Built i...

Страница 5: ...RUN STOP switch e LAN 1 b Reset Button f LAN 2 c COM1 RS 232 COM2 RS 485 2W 4W COM3 RS 485 2W g SD Card Slot d Power Connector h Expansion Connector 81mm 3 19 109mm 4 29 50mm 1 97 a b c d f e g h Top...

Страница 6: ...of time button is pressed ERR LED Action 0 3 seconds No action 3 10 seconds Blinking Reboot PLC and Gateway Over 10 seconds Lights UP Reset to default The projects stored in the unit will be cleared...

Страница 7: ...0 3V lithium battery to keep the RTC running Battery Specification UL Certification Battery Type CR1220 Rated 3V Max Abnormal Charging Current 10mA Working Temperature max 70 C Battery replacement sha...

Страница 8: ...16 N 130mA 0 65 W iR DQ08 R 220mA 1 1 W iR DQ16 N 205mA 1 02 W iR DQ16 P 196mA 0 984 W iR DI16 K 83mA 0 418 W Analog I O iR AQ04 VI 65mA 0 325 W iR AI04 VI 70mA 0 35 W iR AM06 VI 70mA 0 35 W iR AI04 T...

Страница 9: ...select a function from Reboot Download or Upload cMT CTRL01 can be found in the IP HMI Name group box by using the model s IP address even if the PC or laptop is not on the same network UtilityManage...

Страница 10: ...Login page and the language used can be changed in this page Icon Description Displays HMI name Displays system date Displays system time Please note that by default LAN 2 is assigned for Gateway DHC...

Страница 11: ...teway and DNS cMT CTRL01 is equipped with dual Ethernet ports that can be freely assigned as one of the following 1 One Ethernet port for CODESYS LAN1 DHCP and the other one for IIoT Gateway LAN2 DHCP...

Страница 12: ...dentification light The LED indicator of the unit will flash three times when this button is clicked helping user to find the unit 2 3 4 History This tab offers settings related to historical data Cle...

Страница 13: ...P Configure email server and relevant settings Contacts Set email contacts in this tab Update Email Contacts Import the email contacts built using Administrator Tools 2 3 6 Project Management This tab...

Страница 14: ...in the external device to update the project file on cMT CTRL01 2 3 7 System Password Set login password and the password for transferring project file 2 3 8 Enhanced Security The account settings in...

Страница 15: ...more information on EasyAccess 2 0 please see EasyAccess 2 0 User Manual 2 3 10 OPA UA Configure OPC UA settings Please see Chapter 6 OPC UA Web Management Interface in this manual for details 2 3 11...

Страница 16: ...cMT CTRL01 User Manual V1 0 1 13...

Страница 17: ...device connected via COM port Interface Baud rate Data Bits Parity Stop Bits Timeout Parameter 1 Parameter 2 Send ACK Delay Parameters that can be viewed and modified for a device connected via Ethern...

Страница 18: ...age and OS can be updated through Ethernet Launch Utility ManagerEX select Gateway Series Maintenance cMT Gateway OS Update 3 1 Updating Web Package 1 Select an HMI to update OS 2 Select Web package a...

Страница 19: ...sage carefully before you click OK 3 If you click OK the cMT Gateway OS Update window opens again browse for the source file and then click Update 4 The message window below opens please do not turn o...

Страница 20: ...cMT CTRL01 User Manual V1 0 1 17...

Страница 21: ...asic steps are 1 Add a driver into Device List in EasyBuilder Pro 2 Enable OPC UA Server and designate communication address 3 Download the project to HMI The following explains how to set up OPC UA S...

Страница 22: ...New Tag to add tags monitored using OPC UA When finished click OK to leave Step 5 Find the created tags in OPC UA Server window When a large number of tags are used the tags can be exported as a csv e...

Страница 23: ...Project Download PC HMI and set HMI IP address The project can be downloaded via Ethernet Way 2 Download using website Open internet browser IE Chrome Firefox enter cMT CTRL01 s IP address e g 192 168...

Страница 24: ...se see OPC UA server manual 4 4 On line Off line Simulation Running On line or Off line simulation in EasyBuilder Pro helps you examine OPC UA Tag settings In On line simulation cMT Gateway Viewer can...

Страница 25: ...cMT CTRL01 User Manual V1 0 1 22 Step 3 In On line Simulation data in PLC tags will also change...

Страница 26: ...UserManual_en pdf Modbus TCP IP Gateway OPC UA Client MQTT Server MQTT Subscriber MQTT Publisher Administrator Tools Time synchronization NTP Macro Project protection iE XE eMT mTV communication proto...

Страница 27: ...into the address bar of a web browser At the entry page log in with System setting s password Factory default of the password is 111111 Suggested resolution 1024 768 or higher Navigate to the OPC UA c...

Страница 28: ...ctive client connection when shutting down the server will wait for a few seconds before closing off completely In addition both the toggle button and a line of text also indicate the status of the se...

Страница 29: ...trust the certificate from any client connection OPC UA server must be configured with at least one user authentication mode as listed in the following table Authentication Descriptions Anonymous Allo...

Страница 30: ...y available in the OPC UA server New nodes and groups can be added while existing nodes and groups can be edited or deleted For ease of navigation detail information of the currently selected node gro...

Страница 31: ...ll Free Tag Names Siemens S7 1200 1500 Symbolic Addressing etc 6 5 Certificates In this page the user can manage certificates and revocation lists of the OPC UA server Use the dropdown menu to access...

Страница 32: ...e generated automatically if own certificate is absent when server starts up Trusted Client Issuers List of trusted client issuer certificates Supported operation Import Remove Export Trusted User Iss...

Страница 33: ...take effect 6 7 Advanced Additional settings can be configured in the Advanced tab The user can set the trace logging level and specific startup behavior of the OPC UA server Furthermore the trace lo...

Страница 34: ...Package file we prepared and follow these steps for quick installation 1 First get a copy of CODESYS Package file 2 On your PC right click the mouse button and select Open with CODESYS Package Manager...

Страница 35: ...cMT CTRL01 User Manual V1 0 1 32 5 The installed component will be shown in the installation summary...

Страница 36: ...irefox Safari enter cMT CTRL01 s IP address e g 192 168 100 1 and then configure cMT CTRL01 settings 3 Open CODESYS page to see the IP address By default DHCP is used for cMT CTRL01 CODESYS IP 8 2 Cre...

Страница 37: ...ilt in CODESYS to open the settings window 4 Open Scan Network tab CODESYS software will start searching for the CODESYS devices on the same network Select the desired device and then click OK to leav...

Страница 38: ...cMT CTRL01 User Manual V1 0 1 35 5 The project will connect the selected device IP address of the device can be entered in the field shown below...

Страница 39: ...everal tags in PLC_PRG tab and make tag test accumulate automatically 9 2 Exporting Tags 1 Right click on Application in Devices tree and then select Add Object Symbol Configuration use defaults 2 Fin...

Страница 40: ...SYS in the device list 2 Open Tag Manager and click and then click Import Tag to import the xml file built in preceding steps 3 The CODESYS tags can now be found in Tag Manager 4 Create a Numeric obje...

Страница 41: ...dules Chapter10 1 Right click on iBus iBus and then select Add Device 2 Select an iR module and then click Add Device 3 The added device can be found under iBus You may add more modules with this wind...

Страница 42: ...us has two addresses in BYTE type that show low voltage and I O error 5 Open PLC_PRG in Devices tree and configure variables as shown below 6 In Devices tree double click on an iR module name to open...

Страница 43: ...cMT CTRL01 User Manual V1 0 1 40 7 When finished click Online Login to download the project to CODESYS...

Страница 44: ...be found in Devices tree 4 Double click on Ethernet with the current window opened in Devices tree or right click on Ethernet and then select Add Device 5 Click Fieldbusses Modbus Modbus TCP Master M...

Страница 45: ...e Operating System Settings When Use operating System Settings is selected settings on cMT CTRL01 will be used without being changed 9 When CODESYS is already connected go to General tab and click the...

Страница 46: ...cMT CTRL01 User Manual V1 0 1 43 11 Open Modbus Slave Channel tab and create Modbus Variable 12 Open PLC_PRG in Devices tree create tag and set Bool as data type Write a command as shown below...

Страница 47: ...ay cMT CTRL01 supports Modbus TCP IP Gateway which allows CODESYS to access Modbus TCP IP Gateway using Modbus TCP Slave in order to control the devices connected to Modbus TCP IP Gateway On cMT CTRL0...

Страница 48: ...read When setting Modbus Slave Channel Cycle Time can be configured to adjust the frequency at which data is written to the registers For more information on Modbus Gateway please see EasyBuilder Pro...

Страница 49: ...V1 0 1 46 Removing Weintek Built in CODESYS Chapter12 1 Click Tools Packages Manager 2 Find Weintek Built in CODESYS and then click Uninstall 3 Click Next when seeing the window below 4 Removing the...

Страница 50: ...cMT CTRL01 User Manual V1 0 1 47...

Страница 51: ...installed its indicator will light up in red Please try the following 3 methods to solve this situation 1 Click the icon of CODESYS Gateway SysTray in system settings and then click Start Gateway 2 A...

Страница 52: ...firmware 1 Launch Utility Manager and select cMT Series Maintenance CODESYS Firmware Update Browse for the firmware file and click Update 2 Enter cMT HMI s IP address in the website browser and find...

Страница 53: ...cMT CTRL01 User Manual V1 0 1 50 2 Enter cMT HMI s IP address in the website browser and find CODESYS Project update tab Select the files generated in the previous step and click Update...

Отзывы: