HEAT SETTINGS menus
System type
Display
Preset temperatures
(see next page for description of settings)
MAX SUPPLY
Temp
MIN OUTDOOR
Temp
MIN SUPPLY
Temp
MAX OUTDOOR
Temp
Fan-coil
FAN-COIL
190
0
140
70
Finned tube baseboard
FIN BASE
180
0
130
70
Cast iron baseboard
IRN BASE
180
0
120
70
Cast iron radiators
RADIATOR
180
0
120
70
Radiant – slab on grade
RAD SLAB
120
0
80
70
Radiant – thin slab
RAD SLAB
140
0
80
70
Radiant – below floor (staple up)
RADFLOOR
160
0
90
70
Radiant – above floor (sleeper system)
RADFLOOR
140
0
90
70
Custom
CUSTOM
190
0
70
70
Figure 63
HEAT SETTINGS
menus (see Figure 62, page 57 for setting values and descriptions)
See table below
for system type
explanations
Speed settings
— See
page 80 for blower speed
adjustment procedure and
acceptable speeds.