Gas piping — sizing gas lines
Figure 11
Pipe capacity for 0.60 specific gravity
natural gas; pipe length is in equivalent
feet
Gas
pipe
total
length,
feet
Capacity
Cubic feet per hour, natural gas, 0.60 specific gravity
Gas pressure 13” (330 mm) w.c. or less
Pressure drop 0.3 inches (7.6 mm) w.c.
½”
¾”
1”
1¼”
1½”
2”
2½”
10
132
278
520
1050
1600
3050
4800
20
92
190
350
730
1100
2100
3300
30
73
152
285
590
890
1650
2700
40
NA
130
245
500
760
1450
2300
50
NA
115
215
440
670
1270
2000
75
NA
105
175
360
545
1020
1650
100
NA
96
150
305
460
870
1400
150
NA
90
120
250
380
710
1130
Figure 12
Equivalent lengths of straight pipe for
typical gas line fittings
Pipe size
inches
Equivalent length, feet
90° Elbow
Tee
short
radius
long
radius
line
flow
branch
flow
½
3.6
2.2
1.7
4.2
¾
4.4
2.3
2.4
5.3
1
5.2
2.7
3.2
6.6
1¼
6.6
3.2
4.6
8.7
1½
7.4
3.4
5.6
9.9
2
8.5
3.6
7.7
12.0
2½
9.3
4.0
9.3
13.0
Natural Gas:
Pipe sizing for natural gas
1. Size gas piping from meter outlet to entrance of boiler in accor-
dance with Figure 11 and Figure 12.
2. Use total input of all connected appliances. Divide total input in
Btuh by 1,000 to obtain cubic feet per hour of natural gas.
a. Pipe lengths in Figure 11 are equivalent length of straight
pipe. Convert pipe fittings to equivalent lengths using data
from Figure 12.
b. Figure 11 is only for natural gas with specific gravity 0.60, with
a pressure drop through the gas piping as listed in the table.
c. For additional gas pipe sizing information, refer to ANSI Z223.1
(or B149.1 or B149.2 for Canadian installations).
Natural gas supply pressure
1. Pressure required at gas valve inlet pressure port:
a. Maximum: 13” (330 mm) w.c. with no flow (lockup).
b. Minimum gas pressure, with gas flowing (verify during boiler
startup, while boiler is at high fire) — WM97+70: 3½” (89 mm)
w.c.; WM97+110: 4½” (114 mm) w.c.
2. Install 100% lockup gas pressure regulator in supply line if inlet
pressure can exceed 13” w.c. at any time. Adjust lockup regulator
for 13” w.c. maximum.
Propane Gas:
You must follow the instructions, beginning on page 12,
to operate the boiler on propane. Failure to comply could
result in severe personal injury, death or substantial
property damage.
Pipe sizing for propane gas
1. Contact gas supplier to size pipes, tanks and 100% lockup gas
pressure regulator.
Propane supply pressure
1. Adjust propane supply regulator provided by gas supplier for 13”
(330 mm) w.c. maximum pressure.
2. Pressure required at gas valve inlet pressure port:
a. Maximum: 13” (330 mm) w.c. with no flow (lockup).
b. Minimum gas pressure, with gas flowing (verify during boiler
startup, while boiler is at high fire) — WM97+70: 3½” (89 mm)
w.c.; WM97+110: 4½” (114 mm) w.c.