Weil-McLain SVF 1500-3000 Series Скачать руководство пользователя страница 12

SVF

 

Series 1

 

Commercial Condensing Gas-Fired Water Boiler

 - User’s Information Manual

12

Part number 550-100-251/0819

Maintenance procedures — DAILY

Check the boiler area

To prevent potential of severe personal injury, death 

or substantial property damage, 

eliminate all ma-

terials discussed below

 from the boiler vicinity 

and from the vicinity of boiler combustion air inlet. If 

contaminants are found:

•  Immediately remove products from the area. If 

they have been there for an extended period, call 

a qualified service technician to inspect the boiler 

for possible damage from acid corrosion.

•  If products cannot be removed, immediately call a 

qualified service technician to re-pipe vent (and air)

piping and locate vent termination/air intake away 

from contaminated areas.

 

Combustible/flammable 

materials

 

Do not store combustible materials, gasoline or any 

other flammable vapors or liquids near the boiler. 

Remove immediately if found.

 

Air contaminants

 

Products containing chlorine or fluorine, if allowed 

to contaminate the boiler intake air, will cause acidic 

condensate in the boiler. This will cause significant 

damage to the boiler if allowed to continue. Read the 

list of potential materials listed on page 4 of this manual. 

If any of these products are in the room from which the 

boiler takes its combustion air, they must be removed 

immediately or the boiler combustion air (and vent 

termination) must be relocated to another area.

Check the pressure/temperature gauge

1.  Make sure the pressure reading on the boiler pressure/tempera-

ture gauge does not exceed 5 psig less than the relief valve setting.

2.  Contact a qualified service technician if pressure is too high.

DIRECT EXHAUST installations: 

Verify combustion air openings are 

clear and flue is unobstructed

1.  DIRECT EXHAUST INSTALLATIONS Visually inspect all 

combustion air openings. 
a.  Remove any debris or blockage from combustion air louvers.

The combustion air openings must be unobstructed. 

This is the means for combustion and ventilation air to 

be drawn into the boiler room.

Failure to provide proper combustion air can result in 

severe personal injury, death or substantial property 

damage.

2.  Verify that boiler vent discharge is clean and free of obstructions.
3.  Remove any debris on the flue exhaust openings.
4.  If removing the debris does not allow the boiler to operate cor-

rectly afterwards, contact your qualified service technician to 

inspect the boiler and vent/air systems.

DIRECT VENT installations: 

Verify vent/air terminations are 

unobstructed 

(air piped to the boiler from outside)

1.   Verify that boiler vent discharge and air intake are clean and 

free of obstructions.

2.  Remove any debris on the air intake or flue exhaust openings.
3.  If removing the debris does not allow the boiler to operate cor-

rectly afterwards, contact your qualified service technician to 

inspect the boiler and vent/air systems.

Содержание SVF 1500-3000 Series

Страница 1: ...y other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any telephone in your building Immediately call your gas supplier from a n...

Страница 2: ...and use of the control display 5 8 Prevent air contamination Read the list of air contaminants you must avoid If found either remove the products permanently or have your installer relocate boiler ve...

Страница 3: ...e to boiler personnel and or property may result Continual fresh makeup water will reduce boiler life Mineral build up in boiler heat exchanger reduces heat transfer over heats the metal and causes he...

Страница 4: ...er See next page for location of interior boiler manual gas valve External manual gas valve Union Drip leg From gas supply Boiler gas connection Internal manual gas valve SVF Series 1 Commercial Conde...

Страница 5: ...iler ON OFF switch Boiler gas connection Screen display use to monitor boiler operation change heating system setpoints and enable disable burner Boiler gas connection Boiler gas connection Screen dis...

Страница 6: ...SVF Series 1 Commercial Condensing Gas Fired Water Boiler User s Information Manual 6 Part number 550 100 251 0819 The Control display Figure 4 SVF TM boiler s control display...

Страница 7: ...month date year hour and minutes 2 Keeping the date and time current makes sure the control can record problems ac curately Figure 7 SVF TM boiler control display Maintenance notice screens BOILER STA...

Страница 8: ...eset boiler as shown below To reset Press the DOWN or RIGHT arrow The display will go to the STATUS screen SETTINGS will be highlighted Press the DOWN arrow to move down to MANUAL RESET Press ENTER ce...

Страница 9: ...nto the building Pleasereadtheinformationlistedbelow Ifcontaminatingchemicalswillbepresentnearthelocationoftheboiler combustionairinlet haveyourinstallerpipetheboilercombustionairandventtoanotherlocat...

Страница 10: ...ure gauge Verify boiler front door is securely closed MONTHLY Check vent piping Check air piping Check relief valve Check condensate drain system Check automatic air vent PERIODICALLY Test low water c...

Страница 11: ...ed and started annually at the beginning of the heating season by a qualified service technician In addition the maintenance and care of the boiler listed on Figure 9 page 10 and explainedinthismanual...

Страница 12: ...iately or the boiler combustion air and vent termination must be relocated to another area Check the pressure temperature gauge 1 Make sure the pressure reading on the boiler pressure tempera turegaug...

Страница 13: ...line and refill the condensate trap if problem persists regularly Under some circumstances an SVFTM vent system may not produce enough condensate to keep the condensate trap full of liquid If the tra...

Страница 14: ...red indicat ing a low water condition 4 The SVF TM boiler s control will shut down the boiler on manual reset 5 The control display will flash red as shown in Figure 8 page 8 6 Select MANUAL RESET to...

Страница 15: ...charge pipe to ensure that the valve does not weep after the line has had time to drain If the valve weeps lift the seat again to attempt to clean the valve seat If the valve continues to weep afterwa...

Страница 16: ...SVF Series 1 Commercial Condensing Gas Fired Water Boiler User s Information Manual...

Отзывы: