PER Series 3 Electric-Hydronic Boilers Installation Instructions

Mounting the boiler

Normally, the boiler will be installed against a frame or
masonry wall.  If the wall surface is rough or uneven, it
may be necessary to mount plywood on the wall, then
mount the boiler on the plywood.  Refer to
“Dimensions” on page 12 and “Ratings” on page 13, and
note the boiler weight.  Be sure that the wall structure
will support the boiler and its piping.
The 

9

/

16

" top mounting holes and 

5

/

16

" lower mounting

holes are on 16-inch centers to permit installation on
studs in standard wall construction.  The use of ¼" x
2½" lag screws is recommended for mounting the boiler.
The head diameters of the top two screws must not
exceed 

9

/

16

".

1.

Locate the top mounting holes so that the boiler
will be level.   Install the screws so that the heads
protrude ¾" from the wall.

2.

Raise the boiler to mounting position by placing a
board across the bottom of the boiler or by grasping
the lower left and right inside corners. Do not
attempt to lift the boiler by grasping the bottom
jacket cross tie.

3.

Place the top brackets over the lag screws and then
install screws through the lower mounting holes.
The top screws can now be tightened.

Locating the boiler

The compact construction of the electric-hydronic
boiler permits installation in an alcove, storeroom or
other small area.  The location chosen should have
convenient electrical service.
Allow sufficient clearance above and below the boiler
cabinet to permit installation of supply and return
piping. A minimum of 6 inches is required at the top of
the boiler for installation and accessories.  A clearance
of 10 inches is required on the right hand side for
removal of the elements.

General instructions

The Weil-McLain Model PER electric-hydronic boilers
are assembled units designed for use in forced hot water
heating systems. The suggested design temperature rise
through the boiler is 20°F. The PER boiler is a complete
package including the circulator and expansion tank.
Low flow rates through the boiler at elevated
temperatures should be avoided.  The structure to be
heated should be insulated in the conventional manner
used in your area for electrically heated buildings.  Boiler
must be installed in accordance with these instructions
so as not to void our warranty.
Open the boiler crate and check the contents.  In the
event of shortage or damage, notify the transportation
company immediately.

Expansion tank sizing

Undersized expansion tanks cause system water to be
lost from relief valve and makeup water added through
fill valve.  Eventual section failure can result.

If a Fill-Trol system is used, refer to Table 1 for proper sizing.  If Fill-Trol
action is not desired, size the expansion tank according to the water volume
of the system. If a standard closed expansion tank (without a diaphragm)
is used, the air vent tapping on the boiler casting makes a convenient point
of connection. The No. 109 Fill-Trol is furnished as standard equipment.

Table 1

Expansion tank sizing (Tank sizing based on 200 °F
average system temperature.)

Hydrostatic pressure test

Pressure test boiler before attaching piping or electrical supply.
1.

Install air vent in tapping on top of boiler.

2.

Plug remaining tappings, including relief valve opening.

3.

Connect water supply.  Fill boiler and purge all air.  For more than 10
minutes, pressure-test at 1½ times maximum working pressure.

Do not leave boiler unattended.  Cold water fill could
expand and cause excess pressure, resulting in severe
personal injury, death or substantial property damage.

4.

Check for maintained gauge pressure.  Visually check for leaks if gauge
pressure drops.

5.

Drain boiler and repair leaks if found.

Leaks must be repaired at once.  Failure to do so can
damage boiler, resulting in substantial property damage.

6.

Retest boiler after repairing leaks.

7.

Remove testing plugs and air vent.

Do not use petroleum-based cleaning or sealing
compounds in boiler system.  Severe damage to boiler
will result, causing substantial property damage.

Pre-installation

Boiler
model
number

Standard Fill-Trol tank

(for series loop or one-pipe system 

with convector baseboard)

Additional Ex-Trol tank
(for cast-iron radiators or 

cast-iron baseboard)

PER-15

No. 109

No. 15

PER-20

No. 109

No. 15

PER-25

No. 109

No. 15

Note: Gravity systems converted to a forced hot water system usually require 

additional compression tank capacity.

Содержание PER 550-141-396/0801

Страница 1: ...number from the boiler jacket You may list the CP number in the space provided on the Installation and service certificate found on page 9 PER Series 3 Installer Read all instructions before installi...

Страница 2: ...on failure Addition of oxygen and other gases can cause internal corrosion Leaks in boiler or piping must be repaired at once to prevent makeup water Do not add cold water to hot boiler Thermal shock...

Страница 3: ...d The structure to be heated should be insulated in the conventional manner used in your area for electrically heated buildings Boiler must be installed in accordance with these instructions so as not...

Страница 4: ...to the valve Pre installation continued Wiring the boiler Electric shock hazard Can cause severe personal injury or death if power source including service switch on boiler is not disconnected before...

Страница 5: ...ds Call for heat satisfied 5 The thermostat contacts open de energizing the first contactor 2K the circulator relay 1K and the heater in the first thermal time delay H1 6 After a minimum of 10 seconds...

Страница 6: ...MER TRANSFORMER CIRCULATOR EQUIPMENT GROUND Connect wire to last fused terminal WIRE NUTS WIRE NUTS Schematic Wiring Diagram THERMOSTAT OR END SWITCH Note 1 Note 6 Note 6 Electrical shock hazard can c...

Страница 7: ...a shorted coil To isolate the trouble proceed as follows a Check contactor Connect a jumper from terminal 3 of the electronic delay to the transformer wire going to terminal B on the low side of the...

Страница 8: ...utomatic air vent if used 2 Fill the boiler and system to an initial pressure of about 12 pounds per square inch 3 Open automatic air vent one turn if used 4 Starting on the lowest floor open air vent...

Страница 9: ...ed in the Troubleshooting section on page 7 Restore the limit control settings to their recommended values and set the thermostat to the desired room temperature Fill in Installation and service certi...

Страница 10: ...to be lost from relief valve and makeup water added through fill valve Eventual section failure can result If the relief valve opens frequently check the expansion tank If the system has a pressurized...

Страница 11: ...dust respirator N95 This type of respirator is based on the OSHA requirements for fiberglass wool at the time this document was written Other types of respirators may be needed depending on the job si...

Страница 12: ...ns Dimensions 39603 Incoming power 1 conduit 6 2 19 5 8 31 3 16 14 5 16 8 15 16 2 15 16 28 5 8 7 1 16 19 1 16 2 7 16 Automatic air vent 1 Supply Combination pressure temperature gauge Mounting bracket...

Страница 13: ...000 25 5 5 107 240 1 3 1 5 2 215 Notes 1 Provide manual shutoff valves in the system piping at the supply outlet and the return inlet so the boiler can be drained without draining the entire system 2...

Страница 14: ...Description Weil McLain part number Item number Description Weil McLain part number 1 Control tray 428 800 000 6 Jacket element cover plate 428 800 015 2 Boiler casting with insulation 318 806 200 7 J...

Страница 15: ...lay 2 minutes 510 350 211 Thermal delay 30 seconds 510 350 220 Retainer clip for thermal delay 562 650 102 Transformer 511 842 361 Line terminal and fuse block upper 512 050 002 Line terminal and fuse...

Страница 16: ...installed by a heating contractor whose principal occupation is the sale and installation of plumbing heating and or air conditioning equipment These warranties do not cover 1 Components that are par...

Отзывы: