Gas-Fired Boiler — Boiler Manual
Part Number 550-141-186/0703
20
Figure 20
Piping
multiple
steam boilers
Notes
Each boiler has a boiler feed pump controller (not shown). Level controls (Section 6) must be mounted on same side of boiler as return.
Mount each boiler feed pump controller with body mark at the level indicated in Table 4, page 22 and Figure 23, page 23.
Locate system steam supply takeoff outboard from the boiler connecting piping, as shown, to assure liquid in line will flow to trap.
Locate combined header drain as shown. Install strainer and float and thermostatic trap in drain line as shown. Pipe trap outlet to condensate
receiver.
Size the common header piping per ASHRAE recommendations, and in no case smaller than the individual boiler headers.
Pipe the Hartford Loop tee 4" below boiler waterline.
Boiler controls and trim (valves, low water cutoffs, pump controllers, burners, etc.) are omitted in order to emphasize steam and return piping.
Provide a separate feed pump for each boiler. Alternatively, provide a separate automatic valve with end switch and a single feed pump. When
valves are used, activate the valve with the boiler pump controller. Activate the feed pump with the valve end switch.
Manual steam valve or slow opening automatic steam valve, sized to boiler output capacity.
Boiler steam header for single boiler, see page 18.
Install a float and thermostatic trap and strainer off the equalizer of each boiler from 2 to 4 inches above the water line. Connect the trap outlet to
the condensate receiver. The trap will prevent an idle boiler from flooding due to condensed steam from the system.