Weil-McLain Evergreen 220 Скачать руководство пользователя страница 7

Part number 

550-100-268/1220

7

  

CONDENSING

 

GAS

 

BOILER

 — 

 V

ENT

 A

DDENDUM

Direct Exhaust 

(Category II Only) – Vertical

Figure 3 

DIRECT EXHAUST vertical termination

Determine location for vertical termination

1.  Locate the vent termination using the following guide-

lines:

2.  The vent piping must terminate in a coupling as shown 

in Figure 4, page 8. 

3.  Consider the surroundings when terminating the vent:

a.  Position the vent termination where vapors will not 

damage nearby shrubs, plants or air conditioning 

equipment or be objectionable.

b.  The fl ue products will form a noticeable plume as 

they condense in cold air. Avoid areas where the 

plume could obstruct window views.

c.  Prevailing winds could cause freezing of condensate 

and water/ice buildup where fl ue products impinge 

on building surfaces or plants.

d.  Avoid possibility of accidental contact of fl ue prod-

ucts with people or pets.

e.  Do not locate the termination where wind eddies 

could affect performance or cause recirculation, 

such as inside building corners, near adjacent build-

ings or surfaces, window wells, stairwells, alcoves, 

courtyards or other recessed areas.

f.  Locate or guard vent to prevent condensate damage 

to exterior fi nishes.

4.  Maintain clearances as shown in the illustrations in this 

manual section. Also maintain the following:
a.  Vent must terminate:

•  At least 12 inches above roof or snow line as 

shown in Figure 4, page 8. 

•  At least 6 feet from adjacent walls.
•  No closer than 5 feet below roof overhang.
•  At lease 3 feet above any forced air intake within 

10 feet.

•  No closer than 48 inches below or horizontally 

from any door or window or any other gravity 

air inlet.

b.  Do not terminate closer than 4 feet horizontally 

from any electric meter, gas meter, regulator, relief 

valve or other equipment.

5.  Where the vent penetrates the roof, the annular space 

around the penetration must be permanently sealed 

using approved materials to prevent entry of combus-

tion products into the building.

6.  Locate terminations so they are not likely to be damaged 

by foreign objects, such as stones or balls, or subject to 

buildup of leaves or sediment.

7.  Do not connect any other appliance to the vent pipe.

Prepare roof penetration

1.  Vent pipe penetration:

a.  Cut a hole for the vent pipe. For either combustible or 

noncombustible construction, size the vent pipe hole 

at least 0.5” larger than the vent pipe diameter – use a 

7” hole for 6” PVC.

b.  Insert a galvanized metal thimble in the vent pipe 

hole.

2.  Follow all local codes for isolation of vent pipe when 

passing through fl oors, ceilings and roofs.

3.  Provide fl ashing and sealing boots sized for the vent 

pipe and air pipe.

DIRECT EXHAUST — Vertical termination — 

installation sequence overview

Step 1 

Install the boiler.

Step 2 

Determine the proper location for wall penetration for each 

termination. 
•  Prepare roof penetrations before installing vent piping.

•  Finish by attaching external pipe and fi ttings as shown in the 

termination instructions.

•  Install terminations as described in this manual.

•  Support vertical runs on the outside of the building with 

brackets as shown in the termination instructions. 

Step 3 

Install vent piping from boiler to termination.
•  Install a hanger support within 6 inches of any upturn in 

the piping.

•  Install pipe supports every 5 feet on both the horizontal and 

vertical runs.

•  Slope horizontal piping downward toward the boiler at least 

1/4 inch per foot.

Step 4 

Connect the vent piping at the boiler per manual instructions.

6” to 4”

bell reducer

EV-3505E-bw

VENT

VENT

Max.

5 feet

apar

t

(Support, typica

l)

Vertical support, typical
within 6 inches of any
upturn and Max. 5 feet
apart (by others if needed)

*

Double Acting
Barometric Damper
(by others

if needed)

*

Thermal
Spill Switch

(by others if needed)

*

Variable Speed
Vent Inducer

(by others if needed)

Backflow Preventer
(as needed) per Para.1

Содержание Evergreen 220

Страница 1: ...ion includes requires The Vent system for a Category II Evergreen boiler is considered a Designed Engineered vent system and should be designed by a professional using accepted engineering practices i...

Страница 2: ...of a Double Acting Barometric Damper or Modulating Damper to en sure the appropriate negative pressure range is kept for Category II venting The use of this device should be considered in any Enginee...

Страница 3: ...The chimney must be straight with no offsets and the vent and air piping materials must comply with this instruc tion manual The chimney must be fitted with a sealed access opening through which the i...

Страница 4: ...Code for dealing with other con ditions Free area louver allowance The free area of openings means the area after reduction for any installed louvers or grilles Be sure to consider this reduction when...

Страница 5: ...household laundry rooms Adhesives used to fasten building products and other similar products Excessive dust and dirt Areas likely to have contaminants Dry cleaning laundry areas and establishments S...

Страница 6: ...e inch per 3 000 Btuh of all other appliances in the room TWO openings each at least 1 square inch per 4 000 Btuh of all other appliances in the room OR ONE opening each at least 1 square inch per 3 0...

Страница 7: ...e roof the annular space around the penetration must be permanently sealed using approved materials to prevent entry of combus tion products into the building 6 Locate terminations so they are not lik...

Страница 8: ...rs where required at the boiler vent connection 3 See page 36 of Evergreen Boiler Manual for attaching vent and air pipes at the boiler 4 Cut pipe to required lengths 5 Deburr inside and outside of pi...

Отзывы: