background image

Part number 550-100-268/1220

4

  

CONDENSING

 

GAS

 

BOILER

 — 

 V

ENT

 A

DDENDUM

 Direct  Exhaust 

(Category II Only) Boiler room air opening

Combustion air openings for direct exhaust

Provide combustion air openings to boiler 

room and building.

 Combustion and ventilation 

air for direct exhaust boilers is provided from the 

boiler room. Follow all instructions in the Boiler 

manual and this addendum plus all applicable 

codes, providing combustion air openings as speci-

fi ed. Failure to comply could result in severe per-

sonal injury, death or substantial property damage.

1.  Combustion air must be supplied through openings into the 

boiler room, following the instructions in this addendum 

and compliant with all applicable codes. Read the warning in 

Figure 1, page 5, and ensure the air and boiler room will not 

contain contaminated air.

2.  Where the  boiler shares a space with other appliances, the 

combustion air openings must be sized to handle the com-

bined requirements of all appliances in the space.

Sizing combustion air openings

Air openings provide for ventilation (as well as combustion air) 

to prevent overheating of the boiler controls and boiler space. 

Air is also needed for other appliances located in the same space.

Use Figure 2, page 6, selecting the appropriate installation condi-

tions.

Air openings must be sized to handle  all appliances 

and air movers (exhaust fans, etc.) using the air 

supply.

The sizing given in Figure 2, page 6, is based on the National 

Fuel Gas Code, ANSI Z223.1, allowing adequate air openings for 

gravity-vented gas appliances (Category I) in addition to that 

needed for the 

Evergreen

 boiler.

The air openings recommended in Figure 2, page 6, will allow 

adequate ventilation and combustion air provided the boiler room 

is not subjected to negative pressure due to exhaust fans or other 

mechanical ventilation devices.

Refer to the National Fuel Gas Code for dealing with other con-

ditions.

Free area — louver allowance

The free area of openings means the area

after reduction for any 

installed louvers or grilles

Be sure to consider this reduction when 

sizing the air openings.

Special considerations

Tight construction

ANSI Z223.1 defi nes unusually tight construction where:

1.  Walls and ceilings exposed to the outside atmosphere have a 

continuous water vapor retarder with a rating of 1 perm or 

less with openings gasketed, and . . .

2.  Weather-stripping has been added on openable windows and 

doors, and . . .

  Every vent pipe requires a 

bird screen at its 

termination

. Bird screens are not supplied with 

the 

Evergreen

 boiler. Purchase separately from 

Weil-McLain.

3.  Caulking or sealants are applied to areas such as joints around 

windows and door frames, between sole plates and fl oors, be-
tween wall-ceiling joints, between wall panels, at penetrations 
for plumbing, electrical, and gas lines, and in other openings.

For buildings with such construction, provide air openings into 
the building from outside, sized per the appropriate case in Fig-
ure 2, page 6, if appliances are to use inside air for combustion 
and ventilation.

Exhaust fans and air movers

The appliance space must never be under a negative pressure 
unless all appliances are installed as direct vent. Always provide 
air openings sized not only to the dimensions required for the 
fi ring rate of all appliances, but also to handle the air movement 
rate of the exhaust fans or air movers using air from the build-
ing or space.

Motorized air dampers

If the air openings are fi tted with motorized dampers, electrically 
interlock the damper to:

•  Prevent the boiler from fi ring if the damper is not fully open.

•  Shut the boiler down should the damper close during boiler 

operation.

The Evergreen control provides a Proof of Closure function 
which will prevent the boiler from fi ring if the damper is not fully 
open or closes during boiler operation.  Please refer to the Boiler 
Manual for installation and wiring instructions.

  Ensure that the combustion air will not contain 

Содержание Evergreen 220

Страница 1: ...ion includes requires The Vent system for a Category II Evergreen boiler is considered a Designed Engineered vent system and should be designed by a professional using accepted engineering practices i...

Страница 2: ...of a Double Acting Barometric Damper or Modulating Damper to en sure the appropriate negative pressure range is kept for Category II venting The use of this device should be considered in any Enginee...

Страница 3: ...The chimney must be straight with no offsets and the vent and air piping materials must comply with this instruc tion manual The chimney must be fitted with a sealed access opening through which the i...

Страница 4: ...Code for dealing with other con ditions Free area louver allowance The free area of openings means the area after reduction for any installed louvers or grilles Be sure to consider this reduction when...

Страница 5: ...household laundry rooms Adhesives used to fasten building products and other similar products Excessive dust and dirt Areas likely to have contaminants Dry cleaning laundry areas and establishments S...

Страница 6: ...e inch per 3 000 Btuh of all other appliances in the room TWO openings each at least 1 square inch per 4 000 Btuh of all other appliances in the room OR ONE opening each at least 1 square inch per 3 0...

Страница 7: ...e roof the annular space around the penetration must be permanently sealed using approved materials to prevent entry of combus tion products into the building 6 Locate terminations so they are not lik...

Страница 8: ...rs where required at the boiler vent connection 3 See page 36 of Evergreen Boiler Manual for attaching vent and air pipes at the boiler 4 Cut pipe to required lengths 5 Deburr inside and outside of pi...

Отзывы: