background image

Part No. 

550-100-268/1220

Hazard defi nitions

Th e following defi ned terms are used throughout these Instructions to bring attention to the presence of hazards of 

various risk levels or to important information concerning the life of the product.

Indicates presence of hazards that can cause severe personal injury, death or substantial property damage.
Indicates special instructions on installation, operation or maintenance that are important but not related 

to personal injury or property damage.

Vent Category II Addendum Boiler Manual

KEEP THIS ADDENDUM WITH BOILER MANUAL

This Addendum adds to and supercedes items in the “Evergreen Boiler Manual”

(Part Number 550-100-131) and previously released Addenda’s.

Evergreen Boilers 

(EVG 220, EVG 299/300,  and EVG 399)

 can now be vented in a Category II 

confi guration. 

In addition to the 

Evergreen

 boiler’s Category IV rating (positive pressure, likely to condense),  

Evergreen

boilers are approved for Category II (negative pressure, likely to condense) as well. 

This new venting option includes / requires:

•  The Vent system for a Category II 

Evergreen

 boiler is considered a Designed / Engineered vent system 

and should be designed by a professional using accepted engineering practices in accordance to local 
authority having jurisdiction. 

•  Vertical Vent only.
•  Must not be installed into an existing common vent system with other appliances.
•  Combustion air must come from the boiler room.  See Boiler Room Air opening requirements in this 

Addendum.

•  Must increase venting to 6” using a 6” to 4” bell reducer at boiler vent adapter for Category II Vent 

Connection.

•  The Vent System should be designed so that the pressure in the 6” vent pipe immediately following 

the bell reducer is between the ranges provided in the Table 1, page 2, during all running (burner lit) 
conditions (i.e., High Fire through Low Fire). 

•  Flue gas temperature should not exceed 210°F; the boiler will shut down and recycle if it does. The 

fl ue gas temperature should typically be within 20°F of the return water temperature of the boiler. 
If there is the potential for a wide variation in return water temperatures, the lowest possible tem-
perature should be used for any calculations. 

- continued on next page

CONDENSING GAS BOILER

220/299/300/399

Содержание Evergreen 220

Страница 1: ...ion includes requires The Vent system for a Category II Evergreen boiler is considered a Designed Engineered vent system and should be designed by a professional using accepted engineering practices i...

Страница 2: ...of a Double Acting Barometric Damper or Modulating Damper to en sure the appropriate negative pressure range is kept for Category II venting The use of this device should be considered in any Enginee...

Страница 3: ...The chimney must be straight with no offsets and the vent and air piping materials must comply with this instruc tion manual The chimney must be fitted with a sealed access opening through which the i...

Страница 4: ...Code for dealing with other con ditions Free area louver allowance The free area of openings means the area after reduction for any installed louvers or grilles Be sure to consider this reduction when...

Страница 5: ...household laundry rooms Adhesives used to fasten building products and other similar products Excessive dust and dirt Areas likely to have contaminants Dry cleaning laundry areas and establishments S...

Страница 6: ...e inch per 3 000 Btuh of all other appliances in the room TWO openings each at least 1 square inch per 4 000 Btuh of all other appliances in the room OR ONE opening each at least 1 square inch per 3 0...

Страница 7: ...e roof the annular space around the penetration must be permanently sealed using approved materials to prevent entry of combus tion products into the building 6 Locate terminations so they are not lik...

Страница 8: ...rs where required at the boiler vent connection 3 See page 36 of Evergreen Boiler Manual for attaching vent and air pipes at the boiler 4 Cut pipe to required lengths 5 Deburr inside and outside of pi...

Отзывы: