Part Number 550-110-031/0605

EGH-85 & 95 Series 4 and PFG-6 & 7 Series 6 & 7

Lighting instructions — Robertshaw 7000ERHC

FOR YOUR SAFETY READ BEFORE LIGHTING

LIGHTING INSTRUCTIONS

TO TURN OFF GAS TO THE APPLIANCE

Do not try to light any appliance.

Do not touch any electric switch; do not use any phone in
your building.

Immediately call your gas supplier from a neighbor’s phone.
Follow the gas supplier’s instructions.

If you cannot reach your gas supplier, call the fire department.

WHAT TO DO IF YOU SMELL GAS

If you do not follow these instructions exactly, a fire or explosion may result
causing property damage, personal injury or loss of life.

1.

Stop!

  Read the safety information above on this label.

2. Set the thermostat to lowest setting.
3. Turn off all electrical power to the appliance.
4. Depress gas control knob slightly and turn clockwise 

to 

OFF

.

1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to be

performed.

3. Remove front panel.

4. Depress gas control knob slightly and turn clockwise 

to 

OFF

.

5. Replace front panel.

5. Wait five (5) minutes to clear out any gas. Then smell for

gas, including near the floor. If you smell gas, 

STOP!

 Follow

"B"

 in the safety information above. If you don't smell gas,

go to the next step.

6. Remove access panel located above burners.

7. Find pilot — follow metal tube from gas

control. The pilot is between two burners
behind the access panel.

A. This appliance has a pilot, which must be lighted

by hand. When lighting the pilot, follow these
instructions exactly.

B. Before 

LIGHTING

, smell all around the appliance

area for gas. Be sure to smell next to the floor because
some gas is heavier than air and will settle on the
floor. See below.

C. Use only your hand to depress or turn the gas control knob. Never use

tools. If the selector arm will not depress or move by hand, don't try to
repair it, call a qualified service technician. Force or attempted repair
may result in a fire or explosion.

D. Do not use this appliance if any part has been under water. Immediately

call a qualified service technician to inspect the appliance and to replace
any part of the control system and any gas control, which has been
under water.

Note:

Gas control knob cannot be turned to 

OFF

 

unless

knob is depressed slightly. Do not force.

8. Turn gas control knob counterclockwise 

 to 

PILOT

.

9. Depress gas control knob and hold. Immediately light the

pilot with a match. Continue to hold gas control knob in for
about one (1) minute after the pilot is lit.

If pilot can be lit without depressing gas control knob,
turn gas knob clockwise 

 to 

OFF

 and call your service

technician or gas supplier.

10. Release gas control knob. Pilot should remain lit. If pilot goes

out, repeat steps 4 through 10.

If gas control knob stays depressed after release, stop and
immediately call your service technician or gas supplier.

If the pilot will not stay lit after several tries, turn the gas
control knob clockwise 

 to 

OFF 

and call your service

technician or gas supplier.

11. Replace access panel.

12. Turn gas control knob counterclockwise 

 to 

ON

.

13. Turn on all electric power to the appliance.

14. Set thermostat to desired setting.

15. Replace front panel.

Содержание EGH-85 Series

Страница 1: ...servicetechnicianinaccordancewiththisSupplementand all applicable codes and requirements of the authority having jurisdiction Read this Control Supplement completely before beginning the installation...

Страница 2: ...m the boiler jacket Note to the installer The following defined terms are used throughout these instructions to bring attention to the presence of hazards of various risk levels or to important inform...

Страница 3: ...installation EGH 85 95 water boilers 4 5 Control installation PFG 6 7 water boilers 6 7 Control installation EGH 85 95 steam boilers with probe type LWCO 8 9 Control installation EGH 85 95 steam boil...

Страница 4: ...4 Part Number 550 110 031 0605 EGH 85 95 Series 4 and PFG 6 7 Series 6 7 Control installation EGH 85 95 water boilers...

Страница 5: ...age Figure 1 Control installation EGH 85 95 water boilers 1 Mount and wire controls per wiring diagram page 4 and Figure 1 a Attach junction box inside left jacket panel with 8 32 x machine screws and...

Страница 6: ...6 Part Number 550 110 031 0605 EGH 85 95 Series 4 and PFG 6 7 Series 6 7 Control installation PFG 6 7 water boilers...

Страница 7: ...to work on the boiler Failure to comply can cause severe personal injury death or substantial property damage Figure 2 Control installation PFG 6 7 water boilers 1 Mount and wire controls per wiring d...

Страница 8: ...8 Part Number 550 110 031 0605 EGH 85 95 Series 4 and PFG 6 7 Series 6 7 Control installation EGH 85 95 steam boilers...

Страница 9: ...tantial property damage Figure 3 with probe type low water cutoff 1 Mount and wire controls per wiring diagram page 8 and Figure 3 a Attach junction box inside left jacket panel with 8 32 x machine sc...

Страница 10: ...10 Part Number 550 110 031 0605 EGH 85 95 Series 4 and PFG 6 7 Series 6 7 Control installation EGH 85 95 steam boilers...

Страница 11: ...elief c Operating and limit circuit wiring must be 18 gauge or heavier as supplied with the boiler 2 Bring supply wiring to boiler Must be 14 gauge or heavier Checkout procedure 1 Follow all instructi...

Страница 12: ...d When lighting the pilot follow these instructions exactly B Before LIGHTING smell all around the appliance areaforgas Besuretosmellnexttothefloorbecause some gas is heavier than air and will settle...

Страница 13: ...end of the thermopile gas valve fitting d Attach other meter lead to thermopile lead copper surface e Follow Lighting Instruction label on boiler also found in Control Supplement or User s Informatio...

Страница 14: ...30 seconds Vent damper will rotate to closed position Close thermostat contacts Vent damper will rotate to open position Is 24VAC present across gas valve terminals Remove damper harness from damper...

Страница 15: ...nals Open thermostat contacts for 30 seconds Vent damper will rotate to closed position Close thermostat contacts Vent damper will rotate to open position Is 24VAC present across gas valve terminals R...

Страница 16: ...16 Part Number 550 110 031 0605 EGH 85 95 Series 4 and PFG 6 7 Series 6 7 Parts...

Отзывы: