How the BCP-3 operates...

The BCP-3 establishes ambient comfort by varying the tempera-
ture of the heating system's circulating hot water in response to
changes in the outdoor temperature.  In addition, it provides an
outdoor temperature based start/stop and system pump control
for systems with less than 3 boilers.

Two sensors are used, one to monitor the outdoor temperature,
and one to monitor the temperature of the circulating hot water
in the heating system.  When the outdoor temperature falls to
the outdoor starter setting, the
heating system is activated
and the hot water temperature
is increased  proportionally to
meet the need for more heat.
Should it get warmer outdoors,
the hot water temperature is
automatically lowered by the
control.  If the outdoor
temperature continues to rise
to the outdoor starter setting
then the heating system is
turned off.

Because of many physical
characteristics, and the type of
radiation, ie. baseboard or
radiant, heat loss varies.  In
one building, a 1-degree
temperature change outdoors
may require a change of 1
degree in heating water
temperature; for another it may
require a change of 2, 3, or

even 4 degrees in order to gain the desired comfort level.  This
is known as the reset ratio.  The middle chart shows the wide
range of reset ratios available for the BCP-3.

The installer fits the BCP-3 to a specific building by adjusting
the reset ratio curve.  With a curve of 4 (2:1 reset ratio) a 2-
degree change in outdoor  temperature will change the circulat-
ing hot water temperature by 1 degree; at an 11 curve (1:3 reset
ratio) an outdoor change of 1 degree will change the water

temperature by 3 degrees. Most
buildings with baseboard
radiation require a curve of 67,
or 8. Radiant heat applications
usually require a lower curve.

An optional external heat
demand input can be connected
to the BCP-3  This can be
connected to a new or existing
thermostat or switch to shut the
heating system down when the
thermostat is satisfied.

The BCP-3 can control all the
following types of systems: one
boiler with system pump, one
lo/hi fire boiler with system
pump, two boilers with system
pump, or three boilers (system
pump output must be provided
separately).

INSTALLATION/OPERATING INSTRUCTIONS

BCP-3

Hot Water Reset Control

For up to 3 Boilers

Outdoor Temperature (in °F)

70

60

50

40

20

30

0

-10

10

-20

W

a

ter

 Tem

per

atur

e (

in 

°F)

100

120

110

130

140

150

160

180

170

190

200

210

220

12 11

10

9

8

7

6

4

3
2

5

1

1:4 1:3

1:2

1:1.5

1:1.25

1:1

1.25:1

1.5:1

2:1

3:1
4:1

8:1

This manual must only be used by a 

qualified heating installer/service

technician

. Failure to comply could result in severe personal injury, death or

substantial property damage.

W A R N I N G

Part Number 550-141-696/1200

Содержание BCP-3

Страница 1: ...wide range of reset ratios available for the BCP 3 The installer fits the BCP 3 to a specific building by adjusting the reset ratio curve With a curve of 4 2 1 reset ratio a 2 degree change in outdoo...

Страница 2: ...wiring an extension skirt is available Locate the BCP 3 in a convenient location near the unit to be controlled Mount the unit away from excessive heat or cold Ambient operating temperature is from 20...

Страница 3: ...which is rated at 8 Amp max Total output of all stages must not exceed 15A Class 1 voltages must enter the enclosure through a different opening from any Class 2 wiring For on off single stage boiler...

Страница 4: ...ately 5 seconds Minimum Water Temperature Default is 140 F The display will next show the minimum water temperature setting The BCP 3 can not compute a calculated water temperature below this setting...

Страница 5: ...SPLAY SETTINGS Calculated water temperature Center button pressed once This is the water temperature the BCP 3 will stage units to hold It is based on outdoor temperature and the Fine Tune and Reset R...

Страница 6: ...fies for each degree it gets colder outside the Calculated water temperature will raise 1 degree The other Reset Ratios are shown on the first page The Reset Ratio curves start at 70 F At 70 F the BCP...

Страница 7: ...rgize any stages The BCP 3 comes equipped with a factory installed jumper across the HEAT DEMAND terminals DO NOT remove this jumper unless it is being replaced by a dry contact switch This input woul...

Страница 8: ...oss the System Pump output If the wires are continuous the BCP 3 is calling for the System Pump to run Check the pump to determine why it is not circulating One or more of the Boiler Stages does not f...

Отзывы: