INITIAL CONTROL START-UP

• Whenever the BCP-3 is powered up, it will display the software version number and then the current operating parameters.  Each

display will remain on the screen approximately 5 seconds.  If the parameters are correct, there is no need to make any adjust-
ments.

• Once the parameters have been set for a particular application, they will be retained in memory and will not need to be reset.
• Note that if you do change an operating parameter, you will need to reset all the settings (shown on chart on next page).
• An operating parameter can only be changed when it is being displayed in the start-up sequence.  To restart the sequence it is

necessary to remove power to the BCP-3 and then power it again.

• Set the operating parameters as described in sequence below:

°F or °C - Fahrenheit or Celsius Temperature Operation     Default is °F

• If the display shows °F then the BCP-3 will operate in Fahrenheit degrees.
• If the display shows °C then the BCP-3 will operate in Celsius degrees.
• To change the temperature operation, hold down the center button while pushing either the UP or DOWN button to toggle

between the displays of °F and °C.

• When the correct temperature operation is selected, release the buttons and wait approximately 5 seconds.

b_1, 2, 3, or 4 - Output selection     Default is b_3

• If the display shows b_1 then the BCP-3 will control 1 On/Off Boiler and a System Pump.
• If the display shows b_2 then the BCP-3 will control 2 On/Off Boilers and a System Pump.
• If the display shows b_3 then the BCP-3 will control 3 On/Off Boilers.
• If the display shows b_4 then the BCP-3 will control 1 Lo/Hi Boiler and a System Pump.
• To change the boiler output selection, hold down the center button while pushing either the UP or DOWN button to toggle

between the displays the boiler outputs.

• When the correct boiler output is selected, release the buttons and wait approximately 5 seconds.

Minimum Water Temperature     Default is 140°F

•  The display will next show the minimum water temperature setting. The BCP-3 can not compute a calculated water temperature

below this setting, and can not have a set point value below this.

• DO NOT lower this below the default setting of 140°F without contacting your Weil- McLain representative.
• To change the minimum water temperature, hold down the center button while pushing either the UP button to increase the value,

or the DOWN button to decrease the value.

• When the desired minimum water temperature is selected, release the buttons and wait approximately 5 seconds.

DEFAULT SETTINGS

Settings shown in instructions have been selected by Weil-McLain and will provide proper operation for many
installations.

• The BCP-3 comes equipped with default settings which are a good starting point for most installations.
• After the start-up routine has completed, the display will show the system water temperature.
• To display the other settings (see chart next page), repeatedly press the center PRESS TO READ button.
• A setting can only be adjusted when it is being displayed.
• Use the UP and DOWN buttons to adjust the setting.
• The display will always revert back to the actual system water temperature after 30 seconds.
• The default Fine Tune is 0°.  This means the system target temperature will be 100°F at an outdoor temperature of 70°F as shown

on the reset curves on the front page.

• The default Outdoor Starter setting is 60°F.  When the outdoor temperature is above the Outdoor Starter setting, the BCP-3 will

not give heat.

• The default Reset Ratio is curve 7 or 1:1 (see chart

on first page).  This ratio should be a good
starting point for applications with baseboard or
radiators.  If the application has radiant heat, a
lower numbered reset ratio curve should be
selected.

• The default Reaction Time is 5 minutes. This

makes the minimum run time for any stage 2 

1

/

2

 (or

half the reaction time).

Press to scroll

through settings

Default Display:
System Water
Temperature

OUTPUT

UP

DOWN

SELECT SETTING

Press and
hold to adjust

Содержание BCP-3

Страница 1: ...wide range of reset ratios available for the BCP 3 The installer fits the BCP 3 to a specific building by adjusting the reset ratio curve With a curve of 4 2 1 reset ratio a 2 degree change in outdoo...

Страница 2: ...wiring an extension skirt is available Locate the BCP 3 in a convenient location near the unit to be controlled Mount the unit away from excessive heat or cold Ambient operating temperature is from 20...

Страница 3: ...which is rated at 8 Amp max Total output of all stages must not exceed 15A Class 1 voltages must enter the enclosure through a different opening from any Class 2 wiring For on off single stage boiler...

Страница 4: ...ately 5 seconds Minimum Water Temperature Default is 140 F The display will next show the minimum water temperature setting The BCP 3 can not compute a calculated water temperature below this setting...

Страница 5: ...SPLAY SETTINGS Calculated water temperature Center button pressed once This is the water temperature the BCP 3 will stage units to hold It is based on outdoor temperature and the Fine Tune and Reset R...

Страница 6: ...fies for each degree it gets colder outside the Calculated water temperature will raise 1 degree The other Reset Ratios are shown on the first page The Reset Ratio curves start at 70 F At 70 F the BCP...

Страница 7: ...rgize any stages The BCP 3 comes equipped with a factory installed jumper across the HEAT DEMAND terminals DO NOT remove this jumper unless it is being replaced by a dry contact switch This input woul...

Страница 8: ...oss the System Pump output If the wires are continuous the BCP 3 is calling for the System Pump to run Check the pump to determine why it is not circulating One or more of the Boiler Stages does not f...

Отзывы: