8
Drilling Diameter
+0.2 mm
-0.0 mm
Gland Placement Diameter
(mm)
PG7
13.0
18.2
PG9
15.0
21.0
PG11
19.1
26.7
PG13,5
20.9
29.3
PG16
23.0
32.2
PG21
28.8
40.3
PG29
37.5
52.5
PG36
47.5
66.5
PG42
54.5
76.3
PG48
59.8
83.7
• Drill holes using the specified drilling diameters and gland placement di-
ameters. (See table above)
• When using gland plates, only 20% of the material may be removed.
(Note: For guidance, ensure a minimum distance of at least 15 mm be-
tween the individual gland placement diameters.)
• When drilling directly into the enclosure (lid or body) only 10% of the ma-
terial from each individual side may be removed.
(Note: For guidance, ensure a minimum distance of at least 30 mm be-
tween the individual gland placement diameters.)
• If locknuts are to be used, it is essential to decrease the drilling area by
the additional area of the locknut.
• When drilling, avoid ANY deformation, overheating of the enclosure or
gland plate. Ensure that the hole ( the cable gland) is sealed afterwards
according to the relevant ingress protection rating (IP).