background image

Remove four #8-32 pan head screws [1] from 
top corners of floor box assembly and retain.
Remove transition [2] and mounting plate [3] 
assemblies from box and retain.
Install leveling screws [4] as shown in FIGURE A.
Make conduit connections in accordance with 
application and applicable electric codes.
For feed-thru wiring, remove non-metallic 
dividers [5] as necessary.
Reinstall  transition [2] on top of the mounting 
plate assembly [3].  Secure using  #8-32 pan 
head screws [1] in corners.
Cover visible openings and screws that 
penetrate the floor box with duct tape to 
prevent concrete from entering the box.
Position the floor box with the temporary cover
[6] even with slab level.  Use leveling screws [4] 
and wire to keep the floor box from moving 
during concrete pour.  Minimum depth of pour 
is 6.50 inches [165.1 mm]
Verify that flat head screws [7] holding the 
temporary cover [6] are secure.  After 
tightening, cover screw heads with duct tape.
Pour concrete flush to the top of the temporary
cover [6].
 

1.
 
2.
 
3.
4.
  
5.
 
6.
 
 
7.
 
 
8.
 
 
 
 
9.
  
  
10.

BEFORE CONCRETE POUR, SEE FIGURE A

CAUTION:  RISK OF ELECTRICAL SHOCK.  Disconnect power before installing or servicing. 
NOTICE:  For installation by a qualified electrician in accordance with all national and local electrical codes, 
communications standards, the following instructions and any instructions included with individual devices.
NOTICE:  Insure data/communications circuits are separated from lighting/power circuits in accordance with the NEC  and
CE Code requirements.
 
Use with CFBS1R8CVRxx series round covers.

Adjust height of cover support collar flush to just below the finished floor.  Cover support collar is adjustable for 
finished floors of 0 inches to .25 inches [0.0 - 6.4 mm] thick.  Tighten mounting screws [11] to 10 - 15 lbs-in torque 
[1.1 - 1.7 N-m].  For thicker floor finishes use accessory collars (CFB8RCVRR series), sold separately.
Seal the gap around the cover support collar [10] with a continuous bead of electrical grade type RTV silicone sealant 
(SEE FIGURE E).
Use the provided floor gasket or apply a 1/4 inch [6.3 mm] thick continuous bead of electrical type  of RTV silicon 
sealant compound fully around the perimeter on the underside of the flange [12].
Attach flange [12] to the cover support collar [10] using #8-32 flat head screws [13] provided with the cover.

18.
 
 
19.
 
20.
 
21.

Wiring Device - Kellems
Hubbell Incorporated (Delaware)
40 Waterview Dr.
Shelton, CT 06484
1-800-288-6000
www.hubbell-wiring.com

CFB10G55R/CFB10G55RCR   10 GANG RECESSED FLOOR BOX FOR

ROUND COVER   Installation Instructions

PD2594

04/14

ENGLISH

A

FIGURE

E

FIGURE

4

5

3

1

2

6

7

12

13

SEAL ALL AROUND

Содержание CFB10G55R

Страница 1: ...ith all national and local electrical codes communications standards the following instructions and any instructions included with individual devices NOTICE Insure data communications circuits are separated fromlighting power circuits in accordance with the NEC and CE Code requirements Use with CFBS1R8CVRxx series round covers Adjust height of cover support collar flush to just belowthe finished f...

Страница 2: ... If grounded metallic conduit is used connect green grounding lead 9 to grounding terminal on receptacle For a non metallic conduit system pigtail a separate grounding wire to ground both box and receptacle Install devices using appropriate floor box mounting plates FB10MPxx sold separately Use blank plate FB10MPBNK where no device is installed All devices are to be installed in accordance with ma...

Страница 3: ...nform ment aux codes de l lectricit nationaux et locaux les normes de communication les directives qui suivent et toutes directives incluses avec les dispositifs individuels AVIS S assurer que les circuits de donn es communication sont s par s des circuits d clairage d nergie selon les exigences du Code canadien de l lectricit Utiliser avec les couvercles ronds de la s rie CFBS1R8CVRxx Ajuster la ...

Страница 4: ...m tallique mis la terre est utilis connecter le conducteur vert de mise la terre 9 la borne de terre de la prise Pour un conduit non m tallique relier avec un fil s par le fil de MALT pour mettre la terre la bo te et son couvercle Installer les dispositifs en utilisant des plaques de montage FB10MPxx appropri es vendues s par ment et con ues pour les bo tes de plancher Utiliser une plaque pleine F...

Страница 5: ...s circuitos de iluminaci n energ a seg n las exigencias de la Norma oficial mexicana NOM 001 SEDE Usar con tapas redondas de serie CFBS1R8CVRxx Ajustar la altura del collar n de soporte de la tapa a ras apenas por debajo del acabado del piso El collar n de soporte de la tapa es ajustable para pisos terminados de 0 pulgada a 25 pulgada 0 0 6 4 mm de espesor Apretar los tornillos de montaje 11 a 10 ...

Страница 6: ... a tierra 9 al terminal de conexi n a tierra en el recept culo Para un sistema de tubos no met licos enrollar un cable flexible de conexi n a tierra por separado para conectar a tierra tanto la caja como el recept culo Instalar los dispositivos usando las placas de montaje apropiadas para cajas para piso FB10MPxx vendidas por separado Usar una placa ciega FB10MPBNK donde no haya ning n dispositivo...

Отзывы: