Connecting the SAI Distributor
Technical data
Supply voltage
24 V DC
Limit values
18 V DC to 30 V DC
Contact load per pin
2,5 A
Reverse polarity protection
yes
Current input
module approx. 70 mA
Digital inputs
16 channels
Plug-in stations
DI1 to DI16
Grouping
two groups for each eight channels with a common earth
Permissible input voltage
-30 V DC to +30 V DC (protected against polarity reversal)
Input level Low
< 5 V DC acc. to EN 61131-2 Type 1
Input level High
> 15 V DC acc. to EN 61131-2 Type 1
Input current Low
< 15 mA acc. to EN 61131-2 Type 1
Input current High
2 mA to 15 mA acc. to EN 61131-2 Type 1
Input filter
3 ms
Separation of potentials to the module
electronics
none
Display elements
one yellow/red error/status LED per channel
General technical data:
Ambient temperature during operation
0 to +60 °C acc. to EN 61131-2
Ambient temperature during storage
-25 to +85 °C acc. to EN 61131-2
Protection class
IP65 / IP67
GSD file (Device Data Base File)
WIAU0A74.GSD
Dimensions L x B x H
210 x 54 x 32 mm
Weight
325 g
Article order number
1024310000
Article designation
SAI-AU M8 PB GW 16DI
Table 16
Technical data for the SAI-AU M8 PB GW 16DI
5663600000/1.4/09.09
41
Содержание SAI Active Universal Pro Series
Страница 2: ......
Страница 10: ...Notes on Safety 10 5663600000 1 4 09 09...
Страница 11: ...SAI Pro 2 SAI Pro 2 1 Pro Description 12 2 2 PROFIBUS DP 14 5663600000 1 4 09 09 11...
Страница 20: ...Project Planning with the Universal Pro 20 5663600000 1 4 09 09...
Страница 23: ...Mounting SAIs Figure 7 Dimensions of extension I O with digital outputs 5663600000 1 4 09 09 23...
Страница 28: ...Mounting SAIs 28 5663600000 1 4 09 09...
Страница 95: ...Connecting the SAI Distributor 5663600000 1 4 09 09 95...
Страница 106: ...Commissioning the PROFIBUS DP 106 Figure 76 variable table counter value counter stop 5663600000 1 4 09 09...
Страница 177: ......