WEG Molded Case Circuit Breakers - User’s Manual

4

2.  INSTALLATION

The installation procedure consist of inspecting the circuit breaker and, as 
applicable, installing the trip unit, accessories, interphase barriers, and terminals; 
mounting the circuit breaker; connecting the line and load conductors; torquing 
terminals and attaching terminal shields. Circuit breaker frames, trip units, rating 
plugs, accessories, mounting hardware, and unmounted terminals may be supplied 
in separate packages. To install the circuit breaker, perform the following steps.

Note:  UBW600 circuit breakers are factory sealed for reverse feed applications under UL 489. U Lrequires that 

internal accessories be installedat the factory in these types of circuit breakers.

Internal accessory installation in any type of circuit breaker should be done before the 
circuit breaker is mounted and connected. Refer to individual accessory instruction 
leaflets for specific installation instructions on field installable accessories.

1.  Compare nameplate data with existing equipment ratings and system 

requirements to make sure that the circuit breaker is suitable for the intended 
installation. Prior to mounting, confirm that the circuit breaker has not been 
damaged during transit or initial handling.

2.  To install trip unit and any internal accessories, remove installed cover screws 

and cover.

Note:  The circuit breaker handle must be in the tripped or OFF position to remove the cover. Instructions for 

installing the trip unit and accessories are supplied with the devices.

3.  If not already installed, mount trip unit and accessories (if required) in circuit 

breaker frame.

Note:  When required to be removed or replaced, stationary interphase barriers can only be installed removed with 

circuit breaker in the tripped or open position.

4.  After the trip unit and any internal accessories are installed, and with the circuit 

breaker in the tripped position, make sure that stationary interphase barriers are 
properly installed in base. Install cover and secure with pan-head screws. Eight 
screws are used for two and three pole circuit breakers. Ten screws are used for 
four pole circuit breakers. Torque to 20-22 Ib-in (2.26-2.49 N.m.).

5.  If not already installed, mount wire connecting terminals as shown in Figure 2. 

Secure the terminals to the circuit breaker using two pan-head slotted screws 
and lock washers. Torque to 6 to 8 Ib-ft (8.14 to10.85 N.m). With the circuit 
breaker mounted and before the conductors are installed and conductor 
clamping screws inserted, the terminal mounting screws may be checked for 
correct torque.

Содержание UBW600

Страница 1: ...Motors Automation Energy Transmission Distribution Coatings User s Manual WEG Molded Case Circuit Breakers UBW600 ...

Страница 2: ...res The recommendations and information contained herein are based on WEG experience and judgement but should not be considered to be all inclusive or covering every application or circumstance which may arise If any questions arise contact WEG for further information or instructions 1 INTRODUCTION 1 1 GENERAL INFORMATION The UBW600 circuit breaker Figure 1 are 600 V ac maximum rated devices with ...

Страница 3: ...Amperes ln Fixed thermal Adjustable thermal1 Adjust able magnetic instanta neous Multiples of ln 1 Trip unit rating Fixed rating plug Adjustable rating plug Adjustable short time Multiples of ln 1 UBW600 500 5 to 10 600 500 500 600 2 to 8 600 600 Table 1 available trip unit ratings Notes 1 For adjustable thermal trip units the magnetic setting is a multiple of the maximum thermal setting ...

Страница 4: ... circuit breaker has not been damaged during transit or initial handling 2 To install trip unit and any internal accessories remove installed cover screws and cover Note The circuit breaker handle must be in the tripped or OFF position to remove the cover Instructions for installing the trip unit and accessories are supplied with the devices 3 If not already installed mount trip unit and accessori...

Страница 5: ...configuration the circuit breaker can be mounted using different styles of hardware The following steps describe how to mount the circuit breaker using standard hardware When special hardware is needed for example with the motor operator the instruction leaflet describing the accessory also describes the special mounting arrangements 6 To mount the circuit breaker perform the following steps a For...

Страница 6: ... 438 87 33 3 281 83 34 1 325 33 66 1 719 43 66 0 250 6 35 Radius Circuit breaker handle Load end Figure 4 circuit breaker escutcheon cutout dimensions for 3 pole circuit breakers Note Dimensions in inches millimeters Labels with accessory connection schematic diagrams are provided on the side of the circuit breaker c Position circuit breaker on mounting surface d Install circuit breaker mounting s...

Страница 7: ...e terminal cover on circuit breaker cover with mounting screws provided Torque to 20 22 lb in 2 26 2 49 N m Terminal Cat No Terminal material body Screw head type AWG wire range Metric wire range mm Wire type Torque value lb in N m LT3 UBW4001 Aluminum Socket 400 500 2 185 240 Cu Al 275 31 1 Table 2 terminal types Notes 1 Sold in 3 poles kits only 10 When step type terminals Cat No LT3D UBW600 or ...

Страница 8: ...andle and the PUSH TO TRIP button in the trip unit The circuit breaker handle has three positions two of which are shown on the cover with raised lettering to indicate ON and OFF On the handle ON OFF and trip are also shown by a color coded strip for each circuit breaker handle position red for ON white for tripped and green for OFF see Figure 6 Magnetic adjustment button 3 places Thermal magnetic...

Страница 9: ...TIC TRIP UNIT ADJUSTMENT The magnetic element of each pole of the trip unit can be adjusted by rotating the adjustment buttons on the front face of the trip unit with a screw driver The buttons have several settings as indicated on the nameplate with values in multiples of the trip unit ampere rating In as shown in Figure 7 To adjust the setting rotate each button clockwise until arrow on button p...

Страница 10: ...r in the ON position press the PUSH TO TRIP button to mechanically trip the circuit breaker Trip reset and switch circuit breaker ON several times If mechanism does not reset each time the circuit breaker is tripped replace the circuit breaker 4 Check base cover operating handle and handle barrier for cracks chipping and discoloration Circuit breakers should be replaced if cracks or severe discolo...

Страница 11: ...ate WEG selling policies or other contractual agreement between the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and WEG NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILIT...

Страница 12: ... Phone 233 30 2766490 info zestghana com gh INDIA Bangalore Karnataka Phone 91 80 41282007 info in weg net Hosur Tamil Nadu Phone 91 4344 301577 info in weg net ITALY Cinisello Balsamo Milano Phone 39 2 61293535 info it weg net JAPAN Yokohama Kanagawa Phone 81 45 5503030 info jp weg net MALAYSIA Shah Alam Selangor Phone 60 3 78591626 info wattdrive com my MEXICO Huehuetoca Mexico Phone 52 55 53214...

Отзывы: