Parameter
Description
Range of values
Decimal
places
Instance
Class=A2h Attr=5
CIP data type
Net Id
Size
Qty mapped
words
0 = Automatic
1 = Class 10
2 = Class 15
3 = Class 20
4 = Class 25
5 = Class 30
6 = Class 35
7 = Class 40
8 = Class 45
C5.9.7
Motor Data
C5.9.7.1
Insulation Class
940
USINT
940
enum
1
0 = Class A 105
◦
C
1 = Class E 120
◦
C
2 = Class B 130
◦
C
3 = Class F 155
◦
C
4 = Class H 180
◦
C
5 = Class N 200
◦
C
6 = Class R 220
◦
C
7 = Class S 240
◦
C
8 = Class 250
◦
C
C5.9.7.2
Temperature Rise
0 to 200
◦
C
0
942
USINT
942
8bit
1
C5.9.7.3
Ambient Temperature
0 to 200
◦
C
0
941
USINT
941
8bit
1
C5.9.7.4
Locked Rotor Time
1 to 100 s
0
943
USINT
943
8bit
1
C5.9.7.5
Locked Rotor Current
2.0 to 10.0 x
1
944
USINT
944
8bit
1
C5.9.7.6
Heating Time Constant
1 to 2880 min
0
945
UINT
945
16bit
1
C5.9.7.7
Cooling Time Constant
1 to 8640 min
0
946
UINT
946
16bit
1
C5.9.8
Thermal Image
C5.9.8.1
Reset
0 to 8640 min
0
947
UINT
947
16bit
1
C5.10
SSW Short Circuit
C5.10.1
Motor Off
922
USINT
922
enum
1
0 = Inactive
1 = Fault F019
C5.10.2
Motor On
923
USINT
923
enum
1
0 = Inactive
1 = Fault F020
C5.11
Fault Auto-Reset
C5.11.1
Mode
207
USINT
207
enum
1
0 = Off
1 = On
C5.11.2
Time
3 to 600 s
0
208
UINT
208
16bit
1
C6 Configurations\HMI
C6.1
Password
C6.1.1
Password
0 to 9999
0
210
UINT
210
16bit
1
C6.1.2
Password Options
200
USINT
200
enum
1
0 = Off
1 = On
2 = Change Password
C6.2
Language
SSW900
|