Parameterization
SRW 01 | 5-9
5
P013 – Digital Output O1 to O4 Status
Adjustable
Range:
bit 0 = O1
bit 1 = O2
bit 2 = O3
bit 3 = O4
Factory
Setting:
-
Proprieties:
RO
Description:
It monitors the status of the Control Unit (UC) digital outputs.
E.g.: P013 = 12 = 1100b. It means that the digital outputs O3 and O4 are activated.
The parameters P086 and P087 present the status of the Expansion Digital Unit (EDU) digital inputs and outputs,
respectively.
P086 – Digital Inputs I5 to I10 Status
Adjustable
Range:
0 to 63
Factory
Setting:
-
Proprieties:
RO
Description:
It monitors the status of the Expansion Digital Unit (EDU) digital inputs.
E.g.: P086 = 42 = 101010b. It means that the digital inputs I6, I8 and I10 are actuated.
P087 – Digital Outputs O5 to O8 Status
Adjustable
Range:
bit 0 = O5
bit 1 = O6
bit 2 = O7
bit 3 = O8
Factory
Setting:
-
Proprieties:
RO
Description:
It monitors the status of the Expansion Digital Unit (EDU) digital outputs.
E.g., P087 = 10 = 1010b. It means that the digital outputs O5 and O7 are activated.
NOTE!
The contents of the parameters P013 and P087 represent a binary number where each bit corresponds
to one logic state. Its content is showed as binary on the HMI. The content of P012 and P086 are
showed in decimal.
NOTE!
If a communication loss between the Control Unit (UC) and the Expansion Digital Unit (EDU) occurs,
the status of the Expansion Digital Unit (EDU) digital inputs and outputs informed at the parameters
P086 and P087 will be 0 (zero). After the communication is reestablished, before a Control Unit (UC)
reset command is performed, it is possible to verify the status of the Expansion Digital Unit (EDU) digital
inputs through the parameter P086, and the status of the outputs informed through the parameter
P087 remains 0 (zero).