Monitoring
SRW 01 | 6-13
6
P070 – Number of External Fault Trips
Adjustable
Range:
0 to 65535
Factory
Setting:
-
Proprieties:
RO
Description:
It informs the number of trips per external fault.
NOTE!
It is possible to rest the meters P060 to P070, adjusting P204 = 2.
P071 – Trip Status 1 (binary)
Adjustable
Range:
bit0 = PTC
bit1 = Out of Frequency
bit2 = Undercurrent
bit3 = Overcurrent
Factory
Setting:
-
Proprieties:
RO
Description:
It indicates if any protection actuated with Trip.
E.g.: P071 = 1 = 0001b. It means that the SRW 01 switched off (Trip) the motor due to the PTC thermal
protection actuation.
P072 – Trip Status 2 (binary)
Adjustable
Range:
bit0 = Phase Loss (Current)
bit1 = Current Imbalance
bit2 = Earth Fault
bit3 = Overload
Factory
Setting:
-
Proprieties:
RO
Description:
It indicates if any protection actuated with Trip.
E.g.: P072 = 2 = 0010b. It means that the SRW 01 switched off (Trip) the motor due to the current imbalance
protection actuation.
P073 – Trip Status 3 (binary)
Adjustable
Range:
bit0 = Earth Leakage
bit1 = External Fault
bit2 = Trip Test
bit3 = Phase Sequence
Factory
Setting:
-
Proprieties:
RO
Description:
It indicates if any protection actuated with Trip.
E.g.: P073 = 4 = 0100b. It means that the SRW 01 switched off (Trip) the motor due to the Trip test actuation.