Installation and Connection
CPW17 | 11
E
ng
lis
h
3 INSTALLATION AND CONNECTION
3.1 CONNECTIONS
Table 3.1:
Connection descriptions
Description
Type
Pin
Function
Front View
Power supply
IN
A1
AC / DC Positive [+]
IN
A2
AC / DC Negative [-]
Controlled voltage
OUT
S0
Positive reference [+]
Digital inputs
IN
S1
Dual Channel PNP Input
IN
S2
IN
S3
PNP Start Control
Relay outputs
OUT
13-14
23-24
Output Current paths 2
NO contacts
CONNECTION INSTRUCTIONS
The electrical connection of the safety relay for other devices is carried out by fixed terminals with screws. To
ensure the electrical connections integrity the following connection instructions must be considered:
Table 3.2:
Electrical connection instructions
Parameter
Value
Cable section
24 to 12 AWG
0.5 to 2.5 mm²
Cable resistance
≤ 40 Ω
Cable length of control line
≤ 100 m
Connection type
Screw terminals
Tool
Screwdriver slot Nº3
Torque
≤ 0.4 N.m.
ATTENTION!
Ensure that safety relay is turned off before perform the electrical connections. Do not use the safety
relay like supply to external devices.