Installation and Connection
CFW11W | 2-11
Figure 2.13: Grounding points of the UP11
Use the cables with the gauge indicated in Table 2.6 to ground the UP11 power units.
Table 2.7: Grounding cables
Current (A)
Voltage (V)
Duty
Minimum Cross-Section of
the Grounding Cable (mm2)
700
380-480
ND
240
515
HD
150
640
500-690
ND
240
477
HD
150
Содержание CFW-11W
Страница 5: ...General Information CFW11W 1 2 Figure 1 2 Block Diagram of the CFW 11W...
Страница 6: ...General Information CFW11W 1 3 Figure 1 3 UC 11 Main parts Figure 1 4 UP 11 Main parts...
Страница 31: ...Optional Kits CFW11W 4 2...
Страница 38: ...Technical Specifications CFW11W 5 7 5 3 MECHANICAL DATA Figure 5 2 UP11 dimensions mm in...
Страница 41: ......