Installation and Connection
CFW11W | 2-10
Figure 2.12: Output links of the UP11; output connections to the motor [mm(in)]
Use two cables in parallel, with the recommended gauge indicated in the, for connecting the UP11 output
reactor to the output bus bar (motor connection).
Table 2.6: Output cables
Current (A)
Voltage (V)
Duty
Minimum Cables
Cross-Section (mm2)
700
380-480
ND
(2x) 240
515
HD
(2x) 150
640
500-690
ND
(2x) 240
477
HD
(2x) 150
The screw used to fasten the grounding cable of the UP11 is M12X30 (recommended torque: 60 N
∙
m), refer to
Содержание CFW-11W
Страница 5: ...General Information CFW11W 1 2 Figure 1 2 Block Diagram of the CFW 11W...
Страница 6: ...General Information CFW11W 1 3 Figure 1 3 UC 11 Main parts Figure 1 4 UP 11 Main parts...
Страница 31: ...Optional Kits CFW11W 4 2...
Страница 38: ...Technical Specifications CFW11W 5 7 5 3 MECHANICAL DATA Figure 5 2 UP11 dimensions mm in...
Страница 41: ......