l Analog Voltage Regulator AVR-A-OPT-03
30
29 TROUBLESHOOT
Problem
Causes
Corrective Actions
Circulation of reactive power
between generators when
operating in parallel.
Incorrect phases sequence.
CT connection inverted.
Droop adjustment very low.
Connect the phases sequence correctly.
Polarize CT in phase correctly as it shows below:
Increase droop adjustment, rotating trimpot
clockwise (CW).
Generated voltage decreases
when load is applied, and it
doesn’t return.
The speed is falling at the starting
machine.
U/F limiter acting.
Correct speed regulation.
Adjust U/F limiter, by turning
U/F
trimpot
clockwise.
Alternatoroutput voltage doesn't
increase.
Residual Voltage is too low.
Terminals F+ and F- inverted.
With the regulator ON, use external battery
(12Vcc) to force excitation. (*)
Invert F+ and F-.
Generated voltage oscillates at a
no load.
Dynamic incorrectly adjusted.
Alternatorexcitation voltage
excessively low.
Adjust voltage trimpot.
Insert 10
/200W resistor in series with field.
Voltage overshoots.
No sensing voltage.
Power circuit damaged.
Sensing voltage incompatible with
the voltage regulator.
Check if the generator’s phases are present in the
sensing voltage.
Change the regulator.
Use one connection that supplies the right voltage
to the regulator.
Alternator
Load
P1
P2
S1
S2
Содержание AVR-A-OPT-03
Страница 2: ...www weg net l Analog Voltage Regulator AVR A OPT 03 2 ...
Страница 4: ...www weg net l Analog Voltage Regulator AVR A OPT 03 4 ...
Страница 6: ...www weg net l Analog Voltage Regulator AVR A OPT 03 6 ...
Страница 8: ...www weg net l Analog Voltage Regulator AVR A OPT 03 8 ...
Страница 10: ...www weg net l Analog Voltage Regulator AVR A OPT 03 10 ...
Страница 32: ...www weg net Regulador de Tensión Analógico AVR A OPT 03 32 ...
Страница 54: ...www weg net Regulador de Tensión Analógico AVR A OPT 03 54 ANOTACIONES ...
Страница 56: ...www weg net Regulador de Tensão Analógico AVR A OPT 03 56 ...
Страница 58: ......