Terminal Layouts
Unused channels should have a wire link connected between the + and – terminals to prevent an
errors being detected on that channel.
2)
If there is excessive electrical noise, connect the FG terminal to the ground terminal on the unit.
3)
Connect the ground terminals of the LX3V-4TC module and the PLC. Use grounding on the PLC.
4)
The 24V DC built-in supply of the PLC may be used as the power supply.
4.
Installation notes and usage
4.1
Environmental specification
Item
Specification
Be sure to use the crimp-style terminals that satisfy the
dimensional requirements shows in the left figure.
Apply 0.5 to 0.8 N.m (5 to 8 kgf.cm) torque to tighten the
terminals to prevent abnormal operation.
1)
The compensating cables that can be
used
for
connecting
with
the
thermocouple are the following.
Type K: KX-G, KX-GS, KX-H, KX-HS, WX-G,
WX-H, VX-G
Type J: JX-G, JX-H
For every 10Ω of line resistance, the
compensating cable will indicate a
temperature 0.12°C higher than actual.
Check the line resistance before using.
Long compensating cables are more
prone to noise interference, therefore a
short (less than 100m) compensating
cable is recommended.