WeCo 5K3-LV-HV
HeSU 5K3-LV HV
Page 28 of 69
V_1.1_21-Nov-2020_LV-HV
2.5.3.1 Activation of Parallel Batteries (From Master to Slave#4)
Short press the Master power button for one second. The GREEN RUN light should come on. The battery has been activated normally.
Short press the Slave#1 power button for one second. The GREEN RUN light should come on. The battery has been activated normally.
Short press the Slave#2 power button for one second. The GREEN RUN light should come on. The battery has been activated normally.
Short press the Slave#3 power button for one second. The GREEN RUN light should come on. The battery has been activated normally.
Short press the Slave#4 power button for one second. The GREEN RUN light should come on. The battery has been activated normally.
Now all parallel batteries are activated normally and the parallel system is properly powered on.
2.5.3.2 Shutdown of Parallel Batteries
Long press the Master Power button for five seconds. The GREEN RUN light should go off immediately.
The GREEN RUN lights on the slave batteries will not be extinguished immediately.
The RED FAULT lights on the slave batteries will start flashing after ten seconds and the GREEN RUN lights will remain on.
After one minute the RED Fault lights and the GREEN RUN lights on all slave batteries will go off.
The parallel battery system has shutdown properly.
NOTICE
:
In a parallel battery system, we strongly advise not to switch off individual slave batteries. If there is a reason to switch off a slave
battery, we recommend that the procedure described in 6.3.2 of this manual is followed.
Switching off an individual slave battery in a parallel system is possible in an adverse situation, but only as a last resort.