User’s Manual 

SOR 3 

 

 

 

9.0 Placing in Operation 

 
9.1 Preliminary Measures 

 

  Check whether the local supply power is compatible with that of the device (refer to name plate) and 

that the connection value of the conveyor is within the allowable power range. 

  Connect controller according to the delivered connection schematic  

  Set rated value to zero 

  Turn off release (as far as relevant) 

The controller is now basically functional and can be switched on (power, release). 
 

Notice 

With the control device described herein, it is possible to adjust the resonant frequency 
of  the  connected  conveyor.  Because  in  this  case  even  a  slight  rated-value  preset  can 
result in the full amplitude oscillations of the conveyor, one must be especially careful to 
prevent damage to the conveyor due to the limiting operation of the magnet.  
 

The range of the resonant frequency is practically without feedback of the acceleration, but would not be 
useful anyway, since the conveyor can be neither used under load nor would it be controllable. Therefore, 
a certain frequency interval from the resonant frequency must be adjusted. The frequency interval can be 
under as well as over the resonant frequency. 
 
Resonant frequencies: Due to the construction of the spring-mass system of the conveyor, the system 
can resonate at a number of oscillation frequencies. The additional resonance points are at a multiple of 
the desired frequency. In critical cases, the automatic frequency search cannot recognize them; the fre-
quency must then possibly be set by hand. 
 
9.2 Working Frequency of the Built-in Magnets 

Because at small frequency adjustments the current flowing through the magnet may possibly increase, 
by the first usage of the current in the magnet circuit the current should be checked with an effective 
value meter, and the warmth developing in the magnet should be monitored. 
In  order  to  prevent  an  unduly  high  current  passing  through  the  magnet  and  the  possible  overloading  of 
the  magnet,  it  must  be  observed  that  the  magnets  also  operate  within  the  allowable  working  frequency 
range. 
 
9.3 Measurement of the Output Voltage and the Output Current 

Because there is an electronic converter with pulse amplitude modulated switching signals at the device 
output, the voltage and current values cannot be measured with a conventional meter. To measure these 
values, effective value measurement devices must be used; for example, an iron vane instrument (analog 
meter). It is recommended that analog instruments be used, because electronic multi-meters will not indi-
cate reliable value readings in this case. 
 
9.4 Restore Rated Value    

If, after the adjustment process, the device is found to be out of its allowed state, for example limit opera-
tion  or  an  excessively  high  current  flow  which  necessitates  a  quick  main  power  switch-off,  then  by  the 
next power on operation, the adjusted rated value can be reset as follows: 
 
 
With  device  still  switched  off,  depress 

key and then switch on the main power switch. 

 
By this procedure, the previously set rated-value for the oscillation amplitude will be set to zero. Now, the 
rated-value can be again increased or the frequency adjustment can be changed, among other possible 
modifications. 
 

!

 

 

Содержание 133873

Страница 1: ...ACIEK SP KA JAWNA Jana Dlugosza 2 6 Street 51 162 Wroc aw Poland biuro rgbelektronika pl 48 71 325 15 05 www rgbautomatyka pl www rgbelektronika pl DATASHEET www rgbautomatyka pl www rgbelektronika pl...

Страница 2: ...d with a wide variety of tools and having several testing stands at their disposal are a guarantee of the highest quality service OUR SERVICES ENCODERS SERVO DRIVERS LINEAR ENCODERS SERVO AMPLIFIERS C...

Страница 3: ...Schraubautomaten GmbH Hans Urmiller Ring 56 D 82515 Wolfratshausen Tel 0049 8171 406 0 e Mail info weber online com Fax 0049 8171 406 111 www weber schraubautomaten de User s Manual SOR 3 Frequency c...

Страница 4: ...r disassembly work and when fuses are changed or equipment modifications are undertaken Observe the applicable accident prevention and safety regulations for the respective application Before placing...

Страница 5: ...5 8 0 Operating Panel 5 8 1 Adjustment Procedure 5 9 0 Placing in Operation 6 9 1 Preliminary Measures 6 9 2 Working Frequency of the Built in Magnets 6 9 3 Measurement of the Output Voltage and the O...

Страница 6: ...even with supply voltage variations External release input 2 0 Function The operation of the device is achieved by means of a control panel on the front plate Keys and LED display All adjustments can...

Страница 7: ...nal 100 m Standards 61000 6 2 EN 61000 6 4 Due to internal capacitors at the instant of switch on there is a load current impulse Especially when multiple devices are simultaneously switched on the ma...

Страница 8: ...time 0 10 sec 0 1 sec 406 Enable function invert 0 1 En 0 406 Display software version number 001 8 0 Operating Panel 8 1 Adjustment Procedure When depressing the arrow keys a quick depression of the...

Страница 9: ...then possibly be set by hand 9 2 Working Frequency of the Built in Magnets Because at small frequency adjustments the current flowing through the magnet may possibly increase by the first usage of the...

Страница 10: ...e next menu point or scroll to the end of the menu until the rated value again appears on the display 6 The menu can also be directly exited and return to the normal operation is achieved by depressin...

Страница 11: ...switching of the main power switch the device will be reset 12 0 Internal Connection Via the release input the device can be turned on or off with an external signal voltage of 24 V DC Release Supply...

Страница 12: ...ielded output cable to the conveyor must be used 1 2 3 4 1 P E 2 3 1 P E 2 3 Main supply 110 230 V 50 60 Hz PE 3 4 1 1 L 2 N 3 nc 4 PE 1 A1 2 A2 3 Screen 4 PE 1 2 3 PE Output Feeder Enable input 3 GND...

Отзывы: