User’s Manual
SOR 3
4
4.0 Technical Data
Type
SOR 3
Supply power connection 100...230 V, +/- 10 %, 50/60 Hz
Output
0...210 V, 0...3 A / (0...100 V, 0...3 A)
Recommended*
Master fuse
10 A Slow blow
Circuit breaker 16 A, trigger charac-
teristic “D“
Release
Input 24 V, DC
Operating temperature
0...+45 °C
Storage temperature
-10...+80 °C
Installation altitude
1000 m, 0.5 % rated current reduc-
tion for each additional 100 m
Standards
61000-6-2, EN 61000-6-4,
*Due to internal capacitors, at the instant of switch-on there is a load current impulse. Especially
when multiple devices are simultaneously switched on, the master fuses can be activated. For
this reason, slow-blow fuses, or circuit breakers with slow-blow characteristics must be used.
5.0 Order Nomenclature
Identification
ID Number
Brief Description
SOR 3
133873
3 A, Chassis model controller with no additional function
6.0 Conformity Declaration
We declare herewith the conformity with the EMC Guideline
Weber Schraubautomaten GmbH