Status / Error message

Possible cause 

Correction 

INIT

 

Data communication

Initialisation procedure or system blocked. Electrical wiring defective, 

 

interruption in power circuit/short circuit.

Please contact your authorised Webasto Marine dealer.

SEA

 

Sea water flow insufficient

Compressor output limited, compressor constantly switches to low  output due to high pressure level in refrigerant circuit. Cooling mode  only: sea water temperature too high or sea water flow rate too low.  Sea water strainer blocked or no intake. Sea water pump defective.

Check sea water flow rate at sea water outlet. The minimum flow  rate must be maintained. Clean sea water strainer and bleed sea  water circuit. 

BA11

 Required cold water tem- perature not yet reached

Air handler is only switched on when the required cold water tem- perature is reached.

Correction: No action required. The air handler starts up automatical

-

ly.

CA11

 Compressors deactivated

Set compressor(s) in the control setting are not active.

Please contact your authorised Webasto Marine dealer.

AAA Undervoltage

Switch-off in case of undervoltage. Power supply below set under- voltage value for longer than 5 seconds. Cause is probably excessive- ly long cable, overloading or an insufficiently high power generator  output.

Use a on-shore power connection with a more stable power supply.  Use a shorter power cable for the on-shore connection. Switch off  other electrical loads. Please contact your authorised Webasto  Marine dealer.

A01

 

Low pressure compressor 1

Incorrect pressure sensor measurement.

Please contact your authorised Webasto Marine dealer.

Compressor switches off in heating mode: sea water flow rate too  low or sea water too cold (temperature below 6 °C). Sea water  strainer blocked or no intake.

Remove blockage at sea water inlet. Check/clean sea water strainer  and bleed sea water circuit.

Compressor switches off in cooling mode: cold water flow rate too  low.

Check operation of the cold water pump. If fitted, open shut-off cock  valves. Please contact your authorised Webasto Marine dealer.

Refrigerant shortage.

Please contact your authorised Webasto Marine dealer.

Refrigerant circuit blocked.

Operate chiller unit for 5 minutes in heating or cooling mode (if pos

-

sible), then change over operating mode. Switch chiller unit back on  and check whether the fault occurs again.

A02

 

High pressure compressor 1

Pressure switch defective or power circuit interruption/short circuit.

Please contact your authorised Webasto Marine dealer.

Incorrect pressure sensor measurement

Compressor switches off in cooling mode: sea water cooling insuffi- cient. Sea water strainer soiled or no intake.

Remove blockage at sea water inlet. The minimum flow rates must  be complied with. Clean sea water strainer and bleed sea water cir- cuit.

Compressor switches off in heating mode: cold water flow rate too  low. Cold water pump defective. Plate heat exchanger or cold water  circuit blocked. Refrigerant circuit blocked.

Check operation of the cold water pump. If fitted, open shut-off cock  valves. Please contact your authorised Webasto Marine dealer.

Содержание BlueCool V50 M

Страница 1: ...Water Marine Air Conditioning Systems BlueCool V Series EN Valid for BlueCool V50 M as of change index C 2017 Typ V50 M WBCL1203001C Valid for BlueCool V77 T V64 T as of change index B 2017 Typ V64 T...

Страница 2: ...undings Highlight Explanation 3 3 Requirements for the fol lowing necessary action X X Necessary action 1 4 Warranty and liability Webasto shall not assume liability for defects or damage that are the...

Страница 3: ...touch sensitivity of the screen is optimised to direct contact with the fingers The screen may not respond to touch if gloves are worn Tapping outside the touch sen sitive area at the edge of the scre...

Страница 4: ...reen provide infor mation on the system status The symbols are explained in the table Symbol Meaning 1 On Off 2 Temperature 3 Fan 4 Settings 6 Notification 7 Increase values 8 Decrease values 9 AUTO A...

Страница 5: ...n the set setpoint temperature and the room temperature measured by the cabin temperature sensor Note The system only cools under the following conditions cabin tem perature 15 C Setpoint tem perature...

Страница 6: ...c changeover between cooling and heating 9 System settings The operating logic is explained based on the Timer function The explanation also applies to other setting levels or functions Fig 6 1 3 Time...

Страница 7: ...1 6 Standby Sets the BlueCool MyTouch display to standby mode The available functions are Webasto Logo Shows the Webasto logo Customer logo Shows an individual file that can be loa ded onto BlueCool M...

Страница 8: ...our authorised Webasto Marine dealer A01 Low pressure compressor 1 Incorrect pressure sensor measurement Please contact your authorised Webasto Marine dealer Compressor switches off in heating mode se...

Страница 9: ...Please contact your authorised Webasto Marine dealer A10 Cold water temperature sensor Cold water temperature sensor defective or break short circuit in electrical circuit A15 Cold water flow The flo...

Страница 10: ...mpressor temperature sensor Compressor temperature sensor defective or break short circuit in electrical circuit A27 Data communication in verter No data communication between inverter and pc board A2...

Страница 11: ...s at too high a load A39 Cable bridge inverter Compressor 1 switched off because the input is not bypassed open Cable not connected Function of external relay 24V voltage not applied A40 Compressor 1...

Страница 12: ...ulation blocked Secure adequate air or water flow see A01 and or A02 Refrigerant shortage Please contact your authorised Webasto Marine dealer Oil block Refrigerant circuit blocked Filter or expansion...

Страница 13: ...n the Webasto service centre leaflet or the website of the respective Webasto representative of your country Ident No WBCL010825E 08 18 Errors and omissions excepted Webasto Thermo Comfort SE 2017 Web...

Отзывы: